Trane LPC Install And Operation Instructions page 55

Packaged climate changer air handler
Table of Contents

Advertisement

Input and Outputs
This chapter provides information about
the function of inputs and outputs of the
Tracer AH540/541 controller. The Tracer
AH540 is configured at the factory per
unit configuration and order information.
The field-installed Tracer AH541 must be
configured using a Rover service tool
(refer to the Rover Operation and
Programming guide, EMTX-SVX01E-EN,
for more information).
Binary outputs
The Tracer AH540/541 controller has six
binary outputs that are assigned to the
specific functions shown in Table O-GI-2.
The binary outputs are normally-open,
form A relays. The relays act as a switch
by either completing or breaking the
circuit between the load (the end device)
and the 24 Vac power. For example,
when binary input BO1 is energized, 24
Vac is supplied to terminal BO1, which in
turn energizes the supply fan start/stop
relay (see Figure O-GI-14).
Each binary output has a green status
LED on the Tracer AH540/541 controller
board. The LED is off when the relay
contacts are open. The LED is on when
the relay contacts are closed.
When the binary output relay is Off
(contact is open), a multimeter should
measure 0 Vac across the output termi-
nals. When the binary output relay is On
(contacts are closed), a multimeter should
measure 24 Vac across the output
terminals.
Analog outputs
The Tracer AH540/541 controller has five
analog outputs that are assigned to the
specific functions shown in Table O-GI-3
LPC-SVX01C-EN
Operation
Table O-GI-2. Binary outputs functions & locations
Tracer AH540
Tracer AH541
factory
output
terminal
terminal
label
label
label
BO1
TB21/1 OUT
J21
TB21/2 GND
BO2
TB22/1 OUT
J22
TB22/2 GND
BO3
TB23/1 OUT
J23
TB23/2 GND
BO4
TB24/1 OUT
J24
TB24/2 GND
BO5
TB25/1 OUT
J25
TB25/2 GND
BO6
TB26/1 OUT
J26
TB26/2 GND
2 4 V A C
GND
Figure O-GI-14. Tracer AH540 Termination Board Example
Table O-GI-3. Analog output functions & locations
Tracer AH540
Tracer AH541
factory
output
terminal
terminal
label
label
label
AO1
TB11/1 OUT
J1 1
TB11/2 GND
AO2
TB12/1 OUT
J12
TB12/2 GND
AO3
TB13/1 OUT
J13
TB13/2 GND
AO4
TB14/1 OUT
J14
TB14/2 GND
AO5
TB15/1 OUT
J15
TB15/2 GND
AO6
TB16/1
J16
TB16/2
1 Each analog output can be configured for 0–10 Vdc or 2–10 Vdc operation, and normally open or normally closed.
general
information
field
terminal
label
function
BO1
supply fan start/stop
BO2
exhaust fan start/stop
BO3
DX stage 1 or electric stage 4
BO4
DX stage 2 or electric stage 3
BO5
DX stage 3 or electric stage 2
BO4
DX stage 4 or electric stage 1
TB21-1
BO
TB21-2
field
terminal
label
function
AO1
supply fan speed
AO2
cool valve output or
2-pipe changeover
AO3
heat output (water, steam,
or electric heat sequencer)
AO4
face & bypass damper
AO5
outdoor air damper
AO4
not used
maximum
power
output
function
rating
24 Vac
12 VA
ground
24 Vac
12 VA
ground
24 Vac
12 VA
ground
24 Vac
12 VA
ground
24 Vac
12 VA
ground
24 Vac
12 VA
ground
Supply Fan (Start/
maximum
output range
output
default value
1
rating
0 to 10 Vdc
20 mA
ground
2 to 10 Vdc
20 mA
ground
2 to 10 Vdc
20 mA
ground
2 to 10 Vdc
20 mA
ground
2 to 10 Vdc
20 mA
ground
2 to 10 Vdc
20 mA
ground
55