Table 8A
Chilled Solution Reset Schedule based on Zone Temperature
Reset
Amount = Maximum
LSS = ALSS + Maximum
Adjustable
Factory
Preset = 5
3 - 16 F
Reset
Amount = Zero (0)
LSS = ALSS
Table 8B
Chilled Solution Reset Schedule based on Outside Air Temperature
Reset
Amount = Maximum
LSS = ALSS + Maximum
Adjustable
Factory
Preset = 5
3 - 16 F
Reset
Amount = Zero (0)
LSS = ALSS
Active Leaving
Solution Setpoint
Reset
End Temperature
Range 66 - 81
Factory Preset = 75
Active Leaving
Solution Setpoint
Reset
End Temperature
Range 65 - 125
Factory Preset = 70
System Start-Up
Zone Reset Cooling
Start Temperature
Range 66 - 81
Factory Preset = 78
Outside Air Reset Cooling
Start Temperature
Range 65 - 125
Factory Preset = 90
44
Zone
Temperature
OA
Temperature