Advertisement

Troubleshooting
Control unit diagnostics
Fault messages
48
Flow sensor
HC 2
4C
Flow sensor NC
4D
Room tempera-
ture sensor NC
50
DHW sensor top
52
DHW sensor bot-
tom
58
DHW sensor top
5A
DHW sensor bot-
tom
60
Buffer cylinder
sensor
61
Secondary return
sensor
62
Buffer cylinder,
bottom
63
Ext. heat source
64
Mixer ext. heat
source
68
Buffer cylinder
sensor
69
Secondary return
sensor
6A
Buffer cylinder,
bottom
6B
Ext. heat source
6C
Mixer ext. heat
source
A8
Pump HC 1
60
(cont.)
Cause
Lead broken
Short circuit
Lead broken
Short circuit
Lead broken
No DHW circulation
Measures
Check the terminals; replace
the sensor, if required
Check the sensor; replace if
required
Check the terminals; replace
the sensor, if required
Check the sensor; replace if
required
Check the terminals; replace
the sensor, if required
Check the external heating
circuit pump (see page 49);
replace the pump, if required