Commissioning/service reports
Reports of control parameters
Setting parameters
Primary pump ON for
NC
Heat pump
Max. flow temperature
Min. compressor off
Min. runtime
Optimum runtime
Min. return tempera-
ture
Hysteresis T brine
Min. T primary in
Primary pump flow
Secondary pump flow
Electric heater
Power-OFF
Heating with electric
power
Max. flow temperature
Heater rod delay
Electric heating
threshold
E-heating max. stage
Power failure OFF
time
Failure OFF stage
Stage for power-OFF
Internal hydraulics
Heat pump for drying
buildings
Time for drying build-
ings
Ext. heat source for
drying buildings
Flow hysteresis
Internal pump run-on
DHW
DHW cylinder tem-
perature
144
(cont.)
Setting range
No/Yes
25 to 60 °C
00:20 to 30:00 min
2:00 to 30:00 min
00:20 to 18:00 h
1 to 40 °C
1 to 20 K
-10 to 20 °C
00:10 to 16:40 min
00:10 to 16:40 min
No/Yes
No/Yes
5 to 75 °C
0:00 to 5:00 h
10 to 30000 K ∙ min
1 to 3
00:00 to 18:00 h
1 to 3
1 to 3
No/Yes
0 to 30 days
No/Yes
0.5 to 5.0 K
00:10 to 05:00 min
10 to 70 °C
Standard
Commission-
setting
ing
Yes
55 °C
10:00 min-
utes
2:00 minutes
2:00 h
5 °C
5 K
–4 °C
2:00 minutes
2:00 minutes
Yes
Yes
65 °C
0:30 h
300 K ∙ min
3
0:00 h
1
1
No
0 Days
("OFF")
Yes
2.0 K
02:00 min-
utes
50 °C