Control unit diagnostics
Skipping fault messages
To enable adjustments/scans at the
control unit:
1. Open the programming unit flap. All
current fault messages will be dis-
played.
Displaying fault messages
Fault messages
System fault
10
Outside tempera-
ture sensor
18
Outside tempera-
ture sensor
20
Sec. flow sensor
28
Sec. flow sensor
30
Primary in sen-
sor
31
Primary out sen-
sor
38
Primary in sen-
sor
39
Primary out sen-
sor
40
Flow sensor
HC 2
42
External HS
44
Flow sensor NC
45
Room tempera-
ture sensor NC
(cont.)
2. Press "BACK".
The main menu will be displayed.
You can now make adjustments
and scans.
Cause
Control unit processor
faulty
Short circuit
Lead broken
Short circuit
Lead broken
Short circuit
Lead broken
Short circuit
External heat source
faulty
Short circuit
Troubleshooting
Measures
Replace programming unit
Check the sensor; replace if
required
Check the terminals; replace
the sensor, if required
Check the sensor; replace if
required
Check the terminals; replace
the sensor, if required
Check the sensor; replace if
required
Check the terminals; replace
the sensor, if required
Check the sensor; replace if
required
Check external heat source
Check the sensor; replace if
required
59