Single Boiler Systems - Viessmann VITOPLEX 200 Type SX2A Technical Manual

Oil/gas boilers 90 to 2000 kw
Table of Contents

Advertisement

Control units
(cont.)

Single boiler systems

Vitotronic 100, type GC1
11
Vitotronic 200, type GW1
VIESMANN
50
Electronic boiler control unit
■ For constant boiler water temperature
or
Weather-compensated operation in conjunction with the Vitocontrol
control panel and integral heating circuit control unit Vitotronic 200-
H, type HK1S/HK3S (see separate datasheet)
or
Weather-compensated operation in conjunction with an external
control unit
■ For two-stage or modulating burners, if installed
■ With cylinder thermostat
or
Control of a primary store system with mixer assembly (only availa-
ble as an alternative to the control of a constant return temperature
raising facility with a regulated three-way valve)
■ With boiler protection function subject to boiler version:
– Therm-Control
– Shunt pump
– Control of a constant return temperature raising facility with a
regulated three-way valve (only available as an alternative to the
control of a primary store system with mixer assembly)
■ With integral diagnostic system
■ Function extension (accessories):
To default an additional set boiler water temperature via 0 – 10 V
input
■ Via external contacts:
– Requirement to default set boiler water temperature
– Switching ON burner stages 1 and 2
– Changeover stepped/modulating operation
■ With capability to communicate via LON (order a LON communica-
tion module separately)
According to the Energy Savings Order [Germany], a weather-com-
pensated or room temperature-dependent control unit with time pro-
gram for reduced mode must be installed downstream.
Weather-compensated, digital boiler control unit
■ For single boiler systems
■ For two-stage or modulating burners, if installed
■ With time switch with individual and seven-day programs
■ With plain text programming unit
■ With separately adjustable periods
■ With cylinder thermostat
or
Control of a cylinder primary system with mixer assembly (only avail-
able as an alternative to the control of a constant return temperature
raising facility with a regulated three-way valve)
■ With boiler protection function subject to boiler version:
– Therm-Control
– Shunt pump
– Control of a constant return temperature raising facility with a
regulated three-way valve (only available as an alternative to the
control of a cylinder primary system with mixer assembly)
■ With integral diagnostic system
■ A function extension to default the set boiler water temperature via
a 0 - 10 V input can be connected (accessories).
■ Via external contacts:
– Heating program changeover
– Requirement to default set flow temperature
– Blocking the burner
– Changeover stepped/modulating operation
■ With capability to communicate via LON (order a LON communica-
tion module separately)
OIL/GAS BOILERS