lOCkOUT COMMANDS

fANlk
User fan mode lockout configuration
Permissions: Read/Write
Query
Syntax:
Command
Description: Requests the fan lockout configuration setting .
Assignment
Syntax:
Command
Description: Sets the fan lockout configuration setting to [value] .
Example:
Response
Syntax:
Example:
Parameters
value: fan lockout setting code
0: lockout disabled
1: time-limited lockout
2: lockout enabled; no changes allowed
The three fan mode lockout settings provide varying degrees of setpoint lockout . Time-limited lockouts must be enabled in conjunction with
the temporary change period (LKTIME command) .
MODElk
User system mode lockout configuration
Permissions: Read/Write
Query
Syntax:
Command
Description: Requests the mode lockout configuration setting .
Assignment
Syntax:
Command
Description: Sets the mode lockout configuration setting to [value] .
Example:
Response
Syntax:
Example:
Parameters
value: system mode lockout setting code
0: lockout disabled
2: lockout enabled; no changes allowed
The two system mode lockout settings provide varying degrees of setpoint lockout .
SN[#] FANLK?<CR>
SN[#] FANLK=[value]<CR>
SN1 FANLK=0<CR>
SN[#] FANLK=[value]<CR>
SN1 FANLK=0<CR>
Node address 1 responds with a fan lockout setting of disabled .
SN[#] MODELK?<CR>
SN[#] MODELK=[value]<CR>
SN1 MODELK=0<CR>
SN[#] MODELK=[value]<CR>
SN1 MODELK=0<CR>
Node address 1 responds with a system mode lockout setting of disabled .
COS: N/A
Range
[0 – 2]
COS: N/A
Range
[0,2]