TEMPERATURE CONTROl COMMANDS

MODE, M
Control mode
Permissions: Read/Write
Query
Syntax:
Command
Description: Requests the control mode .
Assignment
Syntax:
Command
Description: Sets the control mode to [value] .
Examples:
Response or
Syntax:
COS Message
Description: The thermostat sends the control mode . The [value] parameter is always in the verbose format .
Example:
Parameters
value: control mode
Off mode – Thermostat or Humidistat
OFF, O:
HEAT, H: Heat mode – Thermostat
COOL, C: Cool mode – Thermostat
EMHT, E: Emergency heat mode (heat pump only) – Thermostat
AUTO, A: Auto mode – Thermostat or Humidistat
Humidification – Humidistat
HUMID:
Dehumidification – Humidistat
DEHUM:
The control mode can be changed through the Home Screens for thermostat control or through the Setup Screens for humidity control . If the
control mode is changed at the node, a C7 COS unsolicited message is issued (if C7 is ON) .
36
SN[#] MODE?<CR>
SN[#] M?<CR>
SN[#] MODE=[value]<CR>
SN[#] M=[value]<CR>
SN1 MODE=HEAT<CR>
SN1 M=A<CR>
SN[#] M=[value]<CR>
SN1 M=COOL<CR>
Node address 1 responds with a control mode of Cool .
[OFF, O, HEAT, H, COOL, C, EMHT, E, AUTO, A, HUMID, DEHUM]
COS: C7
Range