3 Functions
3.12

Setpoint channel

The setpoint channel (refer to Fig. 3-39) forms the coupling element between the
setpoint source and the motor control. MICROMASTER has a special characteristic
which allows the setpoint to be entered simultaneously from two setpoint sources.
The generation and subsequent modification (influencing the direction, suppression
frequency, up/down ramp) of the complete setpoint is carried-out in the setpoint
channel.
MOP
ADC
FF
USS
BOP link
USS
COM link
CB
COM link
Setpoint source
Fig. 3-39
3.12.1

Summation and modification of the frequency setpoint (AFM)

Parameter range:
Warnings
Fault
Function chart number:
For applications where the control quantities are generated from central control
systems, fine tuning is often required locally on-site (correction quantity). For
MICROMASTER, this can be very elegantly realized using the summation point
where the main and supplementary (additional) setpoint are added in the setpoint
channel. In this case, both quantities are simultaneously read-in via two separate
or one setpoint source and summed in the setpoint channel. Depending on
external circumstances, the supplementary setpoint can be dynamically
disconnected or switched-in to the summation point (refer to Fig. 3-40). This
functionality can be used to advantage, especially for discontinuous processes.
110
Additonal
setpoint
Main
setpoint

Setpoint channel

P1070 – r1114
-
-
FP5000, FP5200
SUM
AFM
Limit
RFG
Setpoint channel
MICROMASTER 420
Issue 07/04
Motor
control
Motor
control
Operating Instructions
6SE6400-5AA00-0BP0

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents