RUGGEDCOM RX1512
Installation Guide
Section 3.2
Power Supply Wiring and Grounding
The RX1512 features a Phoenix Plug Terminal Block. Both DC power supply and fail-safe relay connections are
made on the same terminal block.
For DC power supply wiring examples, refer to
For fail-safe relay wiring, refer to DC power supply wiring examples, refer to
WARNING!
The RX1512 has one (1) power supply installed. Service personnel must isolate all power supplies
prior to servicing.
Section 3.2.1
RX1512 DC Power Connectors
Figure 35: RX1512 DC Power Connectors
Section 3.2.2
Chassis Ground Connection
The RX1512 chassis ground connection, shown in
screw. It is recommended to terminate the ground connection in a #10 ring lug. Torque on the chassis ground
connection should not exceed 30 in-lbs (3.4 Nm).
Figure 36: Chassis Ground Connection
Power Supply Wiring and Grounding
Section 3.2.3, "DC Power Supply Wiring
Figure 36, "Chassis Ground
Example".
Section 3.3, "Critical Alarm
Connection", uses a #10-32
Chapter 3
Installation
Wiring".
17