Setting Constant Contact
These operators are shipped from the factory with both open and close
operating modes set to constant contact – stop (C – STP) If your unit is set
to Momentary Contact (MOM) Open and/or CLOSE, reset the
operating modes by taking the following steps:
1) Press CAL/RUN to enter calibration mode. Fig. 2.
2) Press SET/CLEAR until display reads "OPEN MODE > C-STP." Fig. 3.
3) Press SCROLL (DN) until display reads "CLOSE MODE." Fig. 4.
4) Press SET/CLEAR until display reads "CLOSE MODE > C-STP."
Fig. 5.
WARNING:
is not used, then the operator will run Constant Contact Close.
Verify close mode is set to "C-STP"and NOT "C-REV"or "MOM"
before continuing.
5) Press CAL/RUN to return to run mode.
IDLE DOWN LIMIT
Door closed -
operator
standing by
Figure 2
GCL-GH
Heavy Duty Operator
If a monitored external reversing device
www.geniecompany.com
OPEN MODE C-STP
Figure 3
CLOSE MODE MOM
Figure 4
CLOSE MODE C-STP
Figure 5