Section 3: Installing The Fireplace; Step 1 Locating The Fireplace - Heat-N-Glo 8000 DVTFL Installer's Manual

Table of Contents

Advertisement

Step 1
Locating the
Fireplace
Minimum Clearances from the Fireplace to
Glass
Front
Floor
36 inches
0
(914 mm)
The diagram below shows space and clearance
requirements for locating a fireplace within a room.
Figure 4. Fireplace Dimensions, Locations, and
Space Requirements
Clearance Requirements
The top, back, and sides of the fireplace are defined
by stand-offs.
Combustible Materials
Back of
Sides of
Fireplace
Fireplace
1/2 inch
1/2 inch
(13 mm)
(13 mm)
The minimum clearance to a perpendicular wall
extending past the face of the fireplace is one inch (25
mm).
For 6000 Series Models, the back of the fireplace may
be recessed 21-1/2 inches (546 mm) into
combustible construction.
For the 8000 DVTFL, the back of the fireplace may be
recessed 24-7/8 inches (641 mm) into combustible
construction.
For the SL-42DVT, the back of the fireplace may be
recessed 16 1/2-inches (419mm) into combustible
construction.
Top of
Fireplace
Ceiling
3-1/2 inches
31 inches
(89 mm)
(787 mm)
3
Installing the
Fireplace
6

Advertisement

Table of Contents
loading

This manual is also suitable for:

6000 dvtfl6000 xlt6000 archSl-42 dvt