3" min.
3" min.
PL vent manufacturer's
firestop spacer and
support
Fig. 14
#8 installing through the ceiling
Through the ceiling vent, follow PLvent manufacturers
recommendations when using wall and ceiling pass
through.
note: do not place joints within wall pass-throughs.
14
P43 Pellet Stove
venting
Storm collar
Flashing
3" min.
No insulation or
other combustible
materials are
allowed within
3" of the pellet
vent pipe. Unless
specified by the
pipe manufacturer
(See Page 7 for
corner installation
clearances)
3" min.
Fig. 16
Minimum flue vent
configuration
It is required that outside air
be installed with this venting
configuration to reduce smoke
and creosote smell in the room
in the event of power failure.
Fig. 15
12" min. wall to outlet
3-90-04301R18_03/13