Fig. 8
Fig. 9
3-90-04301R18_03/13
venting
3 Ft.
to
combustibles
3 Ft.
to combustibles
3 Ft.
to
combustibles
3 Ft.
to combustibles
#1 Preferred method
This method provides excellent venting for normal
operation and allows the stove to be installed closest
to the wall. Two inches from the wall is safe; however,
four inches allows better access to remove the rear
panel. The vertical portion of the vent should be three
to five feet high. This vertical section will help provide
natural draft in the event of a power failure.
note: do not place joints within wall pass-throughs.
#2 Preferred method
This method also provides excellent venting for normal
operation but requires the stove to be installed farther
from the wall. The vertical portion of the vent should
be three to five feet high and at least three inches from
a combustible wall. This vertical section will provide
natural draft in the event of a power failure.
If the stove is installed below grade be sure the vent
termination is at least 18" above grade. The outlet must
also be 1 foot from the house/building.
Note: Do not place joints within wall pass-throughs.
cautiOn
keep combustible materials (such as grass,
leaves, etc.) at least 3 feet away from the flue
outlet on the outside of the building.
12" min. wall to outlet
11
P43 Pellet Stove