Cxm Controls - Heat Controller HP Series Installation, Operation & Maintenance Manual

Residential packaged geothermal heat pump 1 1/2 to 5 tons
Table of Contents

Advertisement

Heat Controller, Inc.
CXM Control Start-up Operation
The control will not operate until all inputs and safety
controls are checked for normal conditions. The
compressor will have a 5 minute anti-short cycle delay
at power-up. The first time after power-up that there is a
call for compressor, the compressor will follow a 5 to 80
second random start delay. After the random start delay
and anti-short cycle delay, the compressor relay will
be energized. On all subsequent compressor calls, the
random start delay is omitted.
Table 6b: Unit Operation
T-stat signal
G
G, Y or Y1
G, Y1, Y2
G, Y1, Y2, W
G, W
G, Y or Y1, O
G, Y1, Y2, O
1
Stage 1 = compressor, fan
Stage 2 = compressor, auxiliary electric heat, fan
2
Cooling = compressor, fan, reversing valve
HP SerieS

CXM CONTROLS

HP
HRH/HRV
PSC fan
Fan only
5
1
Stage 1 heating
1
5
Stage 2 heating
N/A
Emergency heat
2
6
Cooling
N/A
34
Installation, Operation & Maintenance
31