Installation, Operation & Maintenance

CXM Controls

CXM Control
For detailed control information, see CXM Application, Operation
and Maintenance (AOM) manual (part #97B0003N12).
Field Selectable Inputs
Test mode: Test mode allows the service technician to check
the operation of the control in a timely manner. By momentarily
shorting the test terminals, the CXM control enters a 20 minute
test mode period in which all time delays are sped up 15 times.
Upon entering test mode, the status LED will fl ash a code
representing the last fault. For diagnostic ease at the thermostat,
the alarm relay will also cycle during test mode. The alarm relay
will cycle on and off similar to the status LED to indicate a code
representing the last fault, at the thermostat. Test mode can be
exited by shorting the test terminals for 3 seconds.
Retry Mode: If the control is attempting a retry of a fault,
the status LED will slow fl ash (slow fl ash = one fl ash every 2
seconds) to indicate the control is in the process of retrying.
Field Confi guration Options
Note: In the following fi eld confi guration options, jumper wires
should be clipped ONLY when power is removed from the CXM
control.
Water coil low temperature limit setting: Jumper 3 (JW3-FP1 Low
Temp) provides fi eld selection of temperature
limit setting for FP1 of 30°F or 10°F [-1°F or -12°C] (refrigerant
temperature).
Not Clipped = 30°F [-1°C]. Clipped = 10°F [-12°C].
Air coil low temperature limit setting: Jumper 2 (JW2-FP2 Low
Temp) provides fi eld selection of temperature limit setting for
FP2 of 30°F or 10°F [-1°F or -12°C] (refrigerant temperature).
Note: This jumper should only be clipped under extenuating
circumstances, as recommended by
the factory.
Not Clipped = 30°F [-1°C]. Clipped = 10°F [-12°C].
Alarm relay setting: Jumper 1 (JW1-AL2 Dry) provides fi eld
selection of the alarm relay terminal AL2 to be jumpered to 24VAC
or to be a dry contact (no connection).
Not Clipped = AL2 connected to R. Clipped = AL2 dry contact
(no connection).
DIP Switches
Note: In the following fi eld confi guration options, DIP switches
should only be changed when power is removed from the CXM
control.
DIP switch 1: Unit Performance Sentinel Disable - provides fi eld
selection to disable the UPS feature.
On = Enabled. Off = Disabled.
DIP switch 2: Stage 2 Selection - provides selection of whether
compressor has an "on" delay. If set to stage 2, the compressor
will have a 3 second delay before energizing. Also, if set for stage
2, the alarm relay will NOT cycle during test mode.
On = Stage 1. Off = Stage 2
DIP switch 3: Not Used.
DIP switch 4: DDC Output at EH2 - provides selection for DDC
operation. If set to "DDC Output at EH2," the EH2 terminal will
continuously output the last fault code of the controller. If set to
"EH2 normal," EH2 will operate as standard electric heat output.
HTV/HTD/HTH SERIES
On = EH2 Normal. Off = DDC Output at EH2.
NOTE: Some CXM controls only have a 2 position DIP switch
package. If this is the case, this option can be selected by
clipping the jumper which is in position 4
of SW1.
Jumper not clipped = EH2 Normal. Jumper clipped = DDC
Output at EH2.
DIP switch 5: Factory Setting - Normal position is "On." Do not
change selection unless instructed to do so by the factory.
Table 6a: CXM LED And Alarm Relay Operations
Description of Operation
Normal Mode
Normal Mode with UPS Warning
CXM is non-functional
Fault Retry
Lockout
Over/Under Voltage Shutdown
Test Mode - No fault in memory
Test Mode - HP Fault in memory Flashing Code 2
Test Mode - LP Fault in memory Flashing Code 3
Test Mode - FP1 Fault in memory Flashing Code 4
Test Mode - FP2 Fault in memory Flashing Code 5
Test Mode - CO Fault in memory Flashing Code 6
Test Mode - Over/Under
shutdown in memory
Test Mode - UPS in memory
Test Mode - Swapped Thermistor Flashing Code 9
-Flash code 2 = 2 quick fl ashes, 10 second pause, 2 quick
fl ashes, 10 second pause, etc.
-On pulse 1/3 second; off pulse 1/3 second
Figure 27: Test Mode Pins
27
Heat Controller, Inc.
LED
Alarm Relay
On
Open
On
Cycle (closed 5 sec., Open 25 sec.)
Off
Open
Slow Flash
Open
Fast Flash
Closed
Slow Flash
Open (Closed after 15 minutes)
Flashing Code 1
Cycling Code 1
Cycling Code 2
Cycling Code 3
Cycling Code 4
Cycling Code 5
Cycling Code 6
Flashing Code 7
Cycling Code 7
Flashing Code 8
Cycling Code 8
Cycling Code 9
Short test pins
together to enter Test
Mode and speed-up
timing and delays for
20 minutes.