Vertical Installation - Heat Controller HP Series Installation, Operation & Maintenance Manual

Residential packaged geothermal heat pump 1 1/2 to 5 tons
Table of Contents

Advertisement

Installation, Operation & Maintenance
Sound Attenuation for Vertical Units
Sound attenuation is achieved by enclosing the unit
within a small mechanical room or a closet. Additional
measures for sound control include the following:
1. Mount the unit so that the return air inlet is 90° to
the return air grille. Refer to Figure 9. Install a sound
baffle as illustrated to reduce line-of sight sound
transmitted through return air grilles.
2. Mount the unit on a rubber or neoprene isolation pad to
minimize vibration transmission to the building structure.
Figure 9: Vertical Sound Attenuation

VERTICAL INSTALLATION

�������������
����������������������
���������������������������
���������������������������
HP SerieS
Condensate Piping – Vertical Units
Vertical units utilize a condensate hose inside the
cabinet as a trapping loop; therefore an external trap
is not necessary. Figure 10a shows typical condensate
connections. Figure 10b illustrates the internal trap for
a typical vertical heat pump. Each unit must be installed
with its own individual vent and a means to flush or blow
out the condensate drain line. Do not install units with a
common trap and/or vent.
Figure 10a: Vertical Condensate Drain
�����������������
�����
�����������
Figure 10b: Vertical Internal Condensate Trap
������������������
�����
�������������
����
�����������
15
Heat Controller, Inc.
����
�����������������
1/4" per foot (21mm per m)
slope to drain
���������
����������
��������
���� ����
� ���
����
�����������
�����������
���� ����
���� ���������
��������������
������������
��������
����������
������������
���������������