Indoor Unit Installation - Heat Controller VMH 09 Installation Manual

Version c inverterflex ductless mini-split
Hide thumbs Also See for VMH 09:
Table of Contents

Advertisement

Heat Controller, Inc.
Indoor unit installation (wall-mounted type)
1. Installation Plate
A. Mount the installation plate horizontally on struc-
tural parts (studs) of the wall with proper clear-
ance around the installation plate.
B. If the wall is made of brick, concrete or the like,
drill eight (8) 5mm (0.2in.) diameter holes in
the wall.Insert anchor for appropriate mounting
screws.
C. Fit the installation plate on the wall with eight (8)
type "A" screws.
NOTE:
Fit the Installation Plate and drill holes in the wall ac-
cording to the wall structure and corresponding mount-
ing points on the installation plate. The Installation
Plate may be slightly different according to the different
models of indoor unit.
Model
A in. (mm)
<12,000 Btu/h
≥12,000 Btu/h
2. Drill a hole in the wall
A. Determine hole positions according to the dia-
gram detailed in Fig.5. Drill one (1) hole ( 3in.
(65mm)) slanting slightly toward the outdoors,
as shown in Fig. 6.
B. Always use wall hole conduit when drilling metal
grid, metal plate or the like.
3. Connective Pipe and Drainage Installation
A. Run the drain hose sloping downward. Do not
install the drain hose as illustrated in Fig.7.
INSTALLATION MANUAL
B in. (mm)
28 (710)
10 (250)
30 (750)
10 (250)
31 (780)
11 (270)
32 (790)
10 (265)
31 (780)
11 (270)
32 (815)
11 (280)