REFRIGERANT PIPE CONNECTION

Drain joint installation
Fit the seal into the drain elbow, then insert the
drain joint into the base pan hole of outdoor unit,
rotate 90 to securely assemble them.
Connecting the drain joint with an extension drain
hose (locally purchased) is recommended.
hose (Locally purchased), in case of the water
draining off the outdoor unit during the heating
mode.
Refrigerant pipe connection
1. Flaring work
Main cause for refrigerant leakage
is due to defect in the flaring work.
Carry out correct flaring work
using the following procedure:
A: Cut the pipes and the cable.
Use line set kit or copper tubes/pipes
1. Use the piping kit accessory or pipes
purchased locally.
purchased locally.
2. Measure the distance between the indoor
and the outdoor unit.
Cut the pipes/tubes a little longer than
3. Cut the pipes a little longer than the
the measured distance.
measured distance.
Cut the cable 1.5m longer than the pipe/
4. Cut the cable 1.5m longer than the pipe
tube length.
length.
B: Burr removal
1. Completely remove all burrs from the cut
cross section of pipe/tube.
2. Put the end of the copper tube/pipe in a
downward direction as you remove burrs in
order to avoid dropping burrs into the tubing.
C: Putting nut on
Remove flare nuts attached to indoor and
outdoor unit, then put them on pipe/tube
having completed burr removal.(not possible
to put them on after flaring work)
INSTALLATION MANUAL
Copper tube
24
10
VMH InverterFlex Mini-Split
Base pan hole of
Drain joint
Seal
outdoor unit
Fig.46
90
Oblique
Roughness
Fig.47
Pipe
Reamer
Point down
Fig.48
Flare nut
Fig.49
Seal
Drain pipe
Burr