Indoor unit installation

1. Wall Bracket Mounting
A. There are two tabs on the back of the
indoor unit that hold the wall bracket onto
the unit. Press them down with a flat head
screwdriver to release the wall bracket
from the back of the unit.
B. Mount the wall bracket flush on structural
parts (studs) of the wall with proper unit
clearances in consideration. (Fig. 5, 6 and
Fig. 7)
NoTe: Any space between the unit and the
wall may cause noise or vibration.
C. Screw the wall bracket onto the wall with
type "A" self-tapping screws. If the wall
is made of brick, concrete or the like, drill
1/4" (5mm) diameter pilot holes in the wall.
Use anchors in conjunction with mounting
screws.
NOTE:
• Drill holes in the wall according to the stud
locations and corresponding mounting points
on the actual wall bracket that comes with your
unit. Wall brackets may vary by model and
specifications are subject to change.
• It is important to use all screws provided to
secure the wall bracket to the wall.
2. Create opening for refrigerant and
condensate lines
A. Determine hole position according to the
wall bracket that comes with your unit, the
unit's required clearances (Fig. 6 and 7)
and which direction (left/right) the lines will
be routed from the back of your unit (Fig.
11). Drill 2.5"(65mm) hole angled downward
(approx. 45°) toward the outdoors. (Fig. 8).
NoTe: Ensure that neither studs nor
plumbing are located directly behind the
propsed hole location.
B. Always use a conduit to route the piping
though the hole in the wall. Properly seal
the hole after routing the pipes through to
prevent debris, insects, or small animals
from entering.
3. Condensate Drainage
A. Run the drain hose sloping downward. Do not
install the drain hose as illustrated in Fig.9.
B. When extending the drain hose, with locally
purchased hose, insulate the connection
with armaflex or similar pipe insulation
material. (Fig. 10)
9k, 12k Unit
6.38 in. (162 mm)
6 in. (150 mm)
from the wall
or obstacles
2.17 in.
0(55 mm)
6.30 in. (160 mm)
18k Unit
7.44 in. (189 mm)
11.06 in.
(281 mm)
6 in. (150 mm)
2.75 in.
from the wall
0(70 mm)
or obstacles
2.17 in. (55 mm)
6 in. (150 mm)
3.7 in. (94 mm)
3.54 in. (90 mm)
Indoor
Wall Pipe
Do not block water flow by a rise
19
VFH InverterFlex
- Ductless Mini-Split
®
Wall Bracket should be
flush with the interior wall
6 in. (150 mm) away from ceiling
34.09 in. (866 mm)
6.42 in. (163 mm)
2.17 in.
0(55 mm)
3.15 in. (80 mm)
6 in. (150 mm)
away from ceiling
5.67 in. (144 mm)
26.97 in. (685 mm)
22.64 in. (575 mm)
2.75 in.
0(70 mm)
2.17 in. (55 mm)
2.17 in. (55 mm)
5.12 in. (130 mm) 2.72 in. (69 mm)
42.52 in. (1080 mm)
3.54 in. (90 mm)
Outdoor
Seal Pad
Fig. 9
Do not put the end of
drain hose into water
Wall
Pipe Insulation
Extension drain-
hose
Fig. 10
Fig. 5
Fig. 6
6 in. (150 mm)
from the wall
or obstacles
1.38 in.
(35 mm)
Fig. 7
7.28 in.
6 in. (150 mm)
(185 mm)
from the wall
or obstacles
12.56 in.
(319 mm)
Fig. 8