Installing Your Wall Furnace; Locating Wall Furnace And Thermostat - Williams 5508332 Owner's Manual

Counterflow top vent gas wall furnaces
Hide thumbs Also See for 5508332:
Table of Contents

Advertisement

Installing
Your Wall Furnace
The following steps are needed for proper installation and
safe operation of your furnace. If you have any doubts as
to any requirements, always consult your local Heating or
Plumbing Inspector, Building Department or Gas Utility
Company
regarding
regulations,
codes, or ordinances
which apply to the installation of a vented wall furnace.
Obtain professional
help where needed.
The CHECK AND ADJUSTMENTS
on page 24 are vital
to the proper and safe operation of the furnace. Be sure
they are done.
IMPORTANT
For satisfactory and trouble-free operation, be sure to:
1. Properly locate the furnace within the space to be
heated.
2.
Install the furnace in accordance with local codes or
ordinances and instructions
provided.
3.
Maintain minimum clearance: Floor 0 inches or ceil-
ing 4 inches, side wall 4 inches. For exception to
minimum side wall clearance, see Fig. 3, pg. 7.
4.
Be sure to provide enough combustion and ventilation
air.
Locating
Wall Furnace
& Thermostat
Consider the following points before attempting to install
the furnace:
CAUTION
Do not make cut-outs in wall or ceiling before check-
ing in the attic for ceiling joist locations and proposed
venting.
The counterflow vented wall furnaces are shipped ready
to install on the surface of the wall or recessed up to 9-1/4
inches in the wall, with studs 16 inches center-to-center
or stud space can be framed-in to 16 inches, see page
10, Recessed Mounting.
I_[{'kIP_ll
Place the furnace near the center of the space to be
heated for good air circulation. Do not put it behind a door
or draperies.
Do not install the furnace in a closet, alcove, or small
hallway where the furnace could be isolated by closing
doors to the heater space. See Fig. 2 for the minimum
clearances.
Do not install the furnace in a mobile home, trailer, or
recreational vehicle.
The bottom of the furnace may rest directly on a wood or
concrete floor. If floor is other than wood or concrete there
must be a piece of wood or sheet metal under the furnace
that is at least the same size as the bottom of the furnace.
On recessed installations the recessed portion may have
0 inches clearance to combustible
material.
To provide adequate clearance and service access the
front of the furnace must face the open room. Be sure that
gas piping and electrical wiring can be brought to the loca-
tion. See sections covering piping and electrical wiring for
your type of furnace mounting.
Furnace vent must be installed directly to the outdoors so
that combustion gasses will not collect inside the building.
Provide an adequate vent or flue in accordance with local
codes or ordinances and instructions provided by the vent
pipe manufacturer.
Check the minimum spacing needs as shown in Figs. 2
and 3, pages 6 and 7.
The top of the furnace must be at least 4 inches from the
ceiling. See Fig. 2.
With standard furnace discharge
outlet, do not install
closer than 4 inches to intersecting wall. See Fig. 3B,
page 7.
When using optional kits 6703 or 6704 maintain clearances
as shown in Figs. 3A or 3C, page 7.
When using optional kit 6704 maintain clearance as shown
in Figs. 3A and 3F, page 7. Use only optional outlet and
grille kits available from manufacturer.
RNISHED FLOOR
O" MIN.
FOR EXCEPllONS
TO MIN. SIDE
WALL CLF_CE
_RG.S
3A. ,.3C
,'.'_ k 3F
--6--

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents