Toshiba RAS-13UAV-E2 Service Manual page 70

Split wall type
Table of Contents

Advertisement

10-8-3. Indoor unit (Other parts)
No.
Part name
1
Room temp. (TA) sensor
Heat exchanger (TC) sensor
2
Remote control
3
Louver motor
MP24GA
4
Indoor fan motor
10-8-4. Outdoor unit
No.
Part name
1
Compressor
(Model : DA91A1F-45F)
2
Outdoor fan motor
(Model : ICF-140-43-1)
3
Compressor thermo. Bimetal type
(Model : US-622KXTMQO-SS)
4
Outdoor temperature sensor
(TO), discharge temperature
sensor (TD), suction temperature
sensor (TS), outdoor heat
exchanger temperature sensor
(TE)
Checking procedure
Disconnect the connector and measure the resistance value with tester.
(Normal temp.)
Temperature
Sensor
TA, TC (k )
To item of How to judge whether remote control is good or bad of the Judgment
of trouble by symptom.
Measure the resistance value of each winding coil by using the tester.
(Under normal temp. 25°C)
Since judgment of DC motor is difficult on the single motor, refer to 10-5-1. (3)
Checking procedure
Measure the resistance value of each winding by using the tester.
Red
White
Black
Measure the resistance value of winding by using the tester.
Check conduction by using the tester.
Disconnect the connector, and measure resistance value with the tester.
(Normal temperature)
Temperature
Sensor
TA, TC (k )
TGa : Heat pump model only.
TO, TS, TE : Refer to the TA, TC characteristic table in Indoor
(Refer to Table 10-8-3, No.1).
– 69 –
FILE NO. SVM-03008
10°C
20°C
25°C
20.7
12.6
10.0
Position
Resistance value
1 to 2
1 to 3
1 to 4
1 to 5
Position
Resistance value
Red - White
White - Black
Black - Red
Position
Resistance value
Yellow - Pink
For details, refer to Section 10-9.
10°C
20°C
30°C
105
64
41
30°C
40°C
7.9
4.5
380±40
0.51 to 0.57
Under 20°C
5 to 20k
40°C
50°C
27
18