Diagnosis/Process flowchart
A
B
Check
winding of
compressor.
OK
Check
fan motor
NG
position
detect
signal.
OK
Replace
outdoor
fan
motor.
Replace control
board assembly.
Check
NG
compressor
winding
resistance.
OK
Replace
control board.

10-8. How to Check Simply the Main Parts

10-8-1. How to check the P.C. board (Indoor unit)
(1) Operating precautions
1) When removing the front panel or the P.C.
board, be sure to shut off the power supply
breaker.
2) When removing the P.C. board, hold the edge
of the P.C. board and do not apply force to the
parts.
3) When connecting or disconnecting the connec-
tors on the P.C. board, hold the whole housing.
Do not pull at the lead wire.
Item
Check
C
NG
Replace
com-
Operation
pressor.
Replace
compressor.
Contents
Check winding resistance
between phases of
compressor, and resistance
between outdoor frames by
using a tester.
Is not grounded.
Is not short-circuited
between windings.
Winding is not opened.
Remove connector CN300 of
the outdoor fan motor, turn on
the power breaker, and
perform the operation. (Stops
though activation is
prompted.)
Check operation within 2
minutes 20 seconds after
activation stopped.
<Output check of fan motor
position detect signal>
While connecting connector
5P (CN301) for position
detection, using a tester,
measure voltage between
1-5. Between 5-4 : 5 V
(2) Inspection procedures
1) When a P.C. board is judged to be defective,
check for disconnection, burning, or discolora-
tion of the copper foil pattern or this P.C. board.
2) The P.C. board consists of the following 2 parts
a. Main P.C. board part:
DC power supply circuit (5 V, 12 V, 15 V),
Indoor fan motor control circuit, CPU and
peripheral circuits, buzzer, and Driving circuit
of louver.
b. Indication unit of infrared ray receiving
Infrared ray receiving circuit, LED:
To check defect of the P.C. board, follow the
procedure described below.
– 66 –
FILE NO. SVM-03008
Summary
OK if 10M or more
OK if 0.51
0.57
}
(Check by a digital tester.)
a) One or two of three
voltages should be 5 V,
and others should be 0V.
(When all are 0V or 5 V,
it is not accepted.)
b) When rotating the fan
slowly with hands, the
voltage between pins
should move from 0V to 5 V.
(Check it with an analog
tester.)