8-3. Temporary Operation

Temporary Auto operation, existence of Auto
Restart, and Temporary Cooling operation can be
set by the TEMPORARY button of the indoor
controller.
TEMPORARY button
TEMPORARY button
Fig. 8-3-1
Table 8-3-1
TEMPORARY button
OFF
ON
Temporary Auto operation start
After pushing button
for 3 seconds
After pushing button
for 10 seconds
8-3-1. Temporary auto operation
When the TEMPORARY button is pushed, the
Auto operation with set temperature fixed at 25 C
starts. Controlling is same as that of Auto opera-
tion by the remote controller.
When the TEMPORARY button is pushed again,
the operation stops.
During Temporary Auto operation, operation by the
remote controller is accepted.
Using the Auto Restart function, the Temporary
Auto operation starts when power failure is reset.
8-3-2. Temporary cooling operation
When the TEMPORARY operation button keeps
pushed for 10 seconds, Cooling operation of
which compressor motor speed and the indoor fan
speed are fixed starts.
Compressor motor speed :
13 : 30 rps
Indoor fan speed : Low
When the TEMPORARY operation button is
pushed again, the operation stops.
Auto Restart function is unavailable.
Control
Auto Restart
control select
Temporary Cooling
operation start
– 31 –
FILE NO. SVM-03008