Superior SSDVPF-CNE-B Installation Instructions Manual page 23

Ssdv direct-vent gas fireplaces
Hide thumbs Also See for SSDVPF-CNE-B:
Table of Contents

Advertisement

HORIZONTAL VENT FIGURES / TABLES (CONTINUED)
u
When using Secure Flex, use
Firestop / Spacer SF4.5VF
v
When using Secure Flex, use
Firestop / Spacer SF4.5HF
Note:
See Table 9 as an aid in
venting component selection for
a particular range of exterior wall
thicknesses.
H
Maximum
+ H
+ H
1
2
feet
(meter)
feet
5
(1.524)
10
(3.048)
15
(4.572)
20
(6.096)
V + H + H 1 + H 2 = 40 feet (12.2 m) Max
H = 8 feet (2.438 meters) Max.
H + H 1 + H 2 = 20 feet (6.096 meters) Max.
Square termination (SV4.5HT-2) shown
Figure 39
- Side Vent, THREE 90 DEGREE ELBOWS
H 1
v
Wall Firestop / Spacer
(SV4.5HF)
u
When using Secure Flex,
use Firestop / Spacer
SF4.5VF
v
When using Secure Flex,
use Firestop / Spacer
SF4.5HF
Note:
See Table 9 as an aid
in venting component selec-
tion for a particular range of
exterior wall thicknesses.
Figure 4
0- Top Vent, THREE 90 DEGREE ELBOWS
H 2
Table H
V Minimum
H Maximum
(meter)
feet
(meter)
2
(0.610)
1
(0.305)
4
(1.219)
2
(0.610)
6
(1.829)
3
(0.914)
8
(2.438)
4
(1.219)
Square termination (SV4.5HT-2) shown
u
Ceiling Firestop /
Spacer (SV4.5VF)
V 1
v
Wall Firestop
/ Spacer (SV4.5HF)
u
Wall Firestop /
Spacer (SV4.5VF)
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
v
Wall Firestop / Spacer
(SV4.5HF)
H 1
u
Ceiling Firestop /
Spacer (SV4.5VF)
V
Example: If 20 feet total (H+H
+H
) horizontal vent run is needed, then 4 feet minimum
1
2
of (V) vertical vent will be required.
This table shows a 1(V) to 5(H) ratio. For every 1 foot of (V) vertical, you are allowed 5
feet of horizontal run up to a maximum total (H+H
H
H
+H
) horizontal run of 20 feet.
1
2
Table J
V Minimum
H
Maximum
+ H
1
feet
(meter)
feet
5
(1.524)
Elbow Only
5
(1.524)
1
10
(3.048)
2
15
(4.572)
3
20
(6.096)
4
H
+ H
= 20 feet (6.096 m) Max.
1
V
H
+ V
+
+ H
= 40 ft. (12.192 m) Max.
1
1
Example: If 20 feet total (H+H
vent run is needed, then 4 feet minimum
V
of (V) vertical vent will be required.
This table shows a 1(V) to 5(H) ratio. For
every 1 foot of (V) vertical, you are allowed
5 feet of (H+ H
) horizontal run, up to a
1
maximum horizontal run of 20 feet.
An elbow is acceptable as 1 foot of vertical
rise except where an elbow is the only
vertical component in the system. See
Figure 36.
(meter)
(0.305)
(0.610)
(0.914)
(1.219)
) horizontal
1