R Value Calculation 
An easy means of determining if a proposed alternate floor protector meets requirements is 
to follow this procedure: 
Convert specification to R‐value: 
1)
R‐value is given – no conversion is needed  
i
k‐factor is given with a required thickness (T) in inches:  R = 1/k x T 
ii
C‐factor is given:  R = 1/C 
iii
Determine the R‐value of the proposed alternate floor protector: 
2)
Use the correct formula given in step 1 (above) to convert values not expressed as 
i
"R." 
For multiple layers, add R‐values of each layer to determine overall R‐value. 
ii
If  the  overall  R‐value  of  the  system  is  greater  than  the  R‐value  of  the  specified  floor 
3)
protector, the alternate is acceptable. 
EXAMPLE: 
The  specified  floor  protector  should  be  ¾"  thick  material  with  a  k‐factor  of  0.84.    The 
proposed  alternate  is  4"  brick  with  a  C‐factor  of  1.25  over  1/8"  mineral  board  with  a  k‐
factor of 0.29. 
Step (a):  Use formula above to convert specification to R‐value.  
R = 1/k x T = 1/0.84 x .75 = 0.893 
Step (b):  Calculate R of proposed system. 
 
4" brick of C = 1.25, therefore R brick = 1/C =1/1.25 = 0.80 
 
1/8" mineral board of k = 0.29, therefore Rmin.bd. = 1/0.29 x 0.125 = 0.431 
 
Total R = R
Step (c):  Compare proposed system of R of 1.231 to specified R of 0.893.  Since proposed 
system R is greater than required, the system is acceptable. 
Definitions: 
Thermal conductance 
 
 
 
Thermal conductivity 
 
 
 
Thermal resistance 
Page | 16
FLOOR PROTECTION
 + R
brick
mineral board 
=   C   =     _____Btu____ 
                                  (hr)(ft
=   k 
=    __(Btu)(inch)__ 
 
                    (hr)(ft
=   R 
=      (ft
                  Btu   
= 0.8 + 0.431 = 1.231 
=   ____W____ 
2
)(deg F)             (m
=   ___W____     =   ____Btu____ 
2
)(deg F) 
      (m)(deg K)           (hr)(ft)(deg F) 
2
)(hr)(deg F) 
=   (m
 
2
)(deg K) 
2
)(deg K) 