Ups System Output; Environmental Specifications - Eaton POWERWARE 9315 Installation And Operation Manual

500–750 kva
Hide thumbs Also See for POWERWARE 9315:
Table of Contents

Advertisement

PRODUCT SPECIFICATIONS
14.3

UPS System Output

14.4

Environmental Specifications

14-2
EATON Powerware
DC Filtering
UPS Output Capacity
Output Voltage Regulation
Output Voltage
Adjustment
(Nominal +/–5%)
Output Voltage Harmonic
Content
Output Voltage Balance
Output Voltage Phase
Displacement
Output Transients
Frequency Regulation
Synchronous to Bypass
Frequency Slew Rate
Overload Capability
Maximum Output
Capability
Operating Temperature
Operating Altitude
Storage Temperature
Relative Humidity
(Operating and Storage)
Acoustical Noise
Electrostatic Discharge
(ESD) Immunity
®
9315 UPS (500–750 kVA) Installation and Operation Manual
Ripple voltage less than 0.5% peak to peak
100% rated current at 0.8 power factor or 100% rated current at 0.9 power
factor
1% (10% to 100% load)
600 Vac nominal, adjustable from 570 Vac to 630 Vac (60 Hz only)
480 Vac nominal, adjustable from 456 Vac to 504 Vac (60 Hz only)
400 Vac nominal, adjustable from 380 Vac to 420 Vac (50/60 Hz)
3% max THD, 2% max single (linear load)
3% for 100% maximum load imbalance (linear load)
3° for 100% maximum load imbalance (linear load)
5% for 100% load step or removal
0.01 Hz free running
Bypass within voltage limits of +5%, –8% of output setting; bypass within
0.5 Hz
1 Hz per second maximum (adjustable)
125% for 10 minutes
150% for 10 seconds
300% peak for 10 cycles without bypass
0 to 40°C (32–104°F) without derating. The recommended operating
temperature is 25°C (77°F).
Maximum 1500m (5000 ft) at 40°C without derating
–20 to +70°C (prolonged storage above 40°C will cause rapid battery
self-discharge)
95% maximum noncondensing
75 dBA at a 1m distance
Meets IEC 801-2 specifications.