Meters Printout [Ctrl]+[M]; System Information Printout [Ctrl]+[A]; Figure 12-5. System Meters Screen - Eaton POWERWARE 9315 Installation And Operation Manual

500–750 kva
Hide thumbs Also See for POWERWARE 9315:
Table of Contents

Advertisement

COMMUNICATION
12-8
EATON Powerware
12.4.3

Meters Printout [Ctrl]+[M]

The [Ctrl]+[M] key sequence prints the current readings of the UPS system meters.
The Input area shows the phase-to-phase voltage, frequency, and phase current of
the incoming utility, followed by the kVA, kW, and power factor measurements. The
output area shows the same information for the power being output by the UPS. The
Bypass area shows the phase-to-phase voltage of the bypass source. The Battery
area displays the DC voltage (V) and the DC current (I). Figure 12-5 shows a sample
System Meters printout.
UPS System Normal
Alarm:
None
Notice:
None
VAB
VBC VCA
480
480 480
IA
640
KVA
530
VAB
480
12.4.4

System Information Printout [Ctrl]+[A]

The [Ctrl]+[A] key sequence prints a listing of all available serial data. This printout
contains the information shown on the Event History Log and System Meters screens
of the UPS (see Figure 12-4 and Figure 12-5).
®
9315 UPS (500–750 kVA) Installation and Operation Manual
Uninterruptible Power System
Input
FREQ
VAB
60.0
480
IB
IC
IA
640
640
480
KW
PF
505
0.95
Bypass
VBC
VCA
480
480

Figure 12-5. System Meters Screen

S
164201691 Rev 1 www.powerware.com
03 NOV 1997
14:22:45
Output
VBC
VCA
FREQ
480
480
60.0
IB
IC
IN
480
480
0
KVA
KW
PF
400
320
0.80
Battery
V
I
+
540
0