78
Appendix B:
Appendix B:
Network Register Map
The following tables list the DeviceNet explicit addressing to access inverter parameters.
Each parameters address consists of Class ID, Instance, and Attribute. The host will also
need to use the Size (number of bytes) in the request. Most of the parameters provide
both Get and Set access (denoted by "G/S") in the tables).
The inverter returns scalar values in decimal format. The scale factors are presented in
the Scaling column. To get a parameter's actual value, the host computer will need to
divide the data by the scale factor (unless it is "1"). The result will be a decimal number
with an integer part and a decimal (fractional) part.
Main Profile Parameters and Basic Inverter Data
"D" Group Parameters and
Basic Inverter Data
Func.
Code
—
Rated capacity
—
Input AC voltage class
—
Rated output current
—
Inverter status
D_01 Output frequency monitor
D_02 Output current monitor
D_03 Rotation direction monitor
D_05 Intelligent input terminal status
Name
Inst Attr Size
1
1
1
1
1
1
1
1
DeviceNet Class ID = 100
Range
100
1
1 0.2 kW
2 0.4 kW
3 0.55 kW
4 0.75kW
5 1.1 kW
6 1.5 kW
7 2.2 kW
8 8.3 kW
9 3.7 kW
10 4.0 kW
11 5.5 kW
12 7.5 kW
101
1
1 200V
2 400V
102
2
0.00 – 655.35A
103
1
0 – 255
104
2
0.01 – 360.00Hz
105
2
0.00 – 655.35A
106
1
1 forward
2 reverse
108
1
0 open
1 close,
Bit 0 = terminal 1
Bit 1 = terminal 2
Bit 2 = terminal 3
Get/
Scaling
Set
—
Get
—
Get
100
Get
1
Get
100
Get
10
Get
—
Get
—
Get