e. Now turn OFF the FW Run bit (bit 1) in Word 0 as shown below. The motor will
now stop.
MSB
Word 0
0 0 0 0
f. To demonstrate another control bit, turn on the RV Run bit (bit 1) as shown
below. The motor will now run in the reverse direction.
MSB
Word 0
0 0 0 0
g. Now turn OFF the RV Run bit (bit 1) in Word 0 as shown below. The motor will
now stop.
MSB
Word 0
0 0 0 0
h. Finally, turn OFF the Network Control bit (bit 5) and the Network Reference bit
(bit 6) as shown below. Notice that the inverter's Run Key Enable LED now turns
ON, indicating that the inverter's control source is local (keypad or terminal).
MSB
Word 0
0 0 0 0
The second control sequence is complete. The host computer controlled the inverter with
Run/Stop (both directions), and also supplied the profile parameter values for output
frequency / accel / decel.
WARNING: Your application may require stopping the motor suddenly, in certain
conditions, to avoid injury to personnel or equipment damage. If so, be sure to configure
the [STP] input terminal on the inverter, described in "Three-wire Interface Operation"
on page 34. This will provide a way for the control environment at the inverter to stop
the motor, should the host computer fail to turn the motor OFF when required.
High byte
LSB
MSB
0 0 0 0
0 1 1 0
Network Reference
Network Control
High byte
LSB
MSB
0 0 0 0
0 1 1 0
Network Reference
Network Control
High byte
LSB
MSB
0 0 0 0
0 1 1 0
Network Reference
Network Control
High byte
LSB
MSB
0 0 0 0
0 0 0 0
Network Reference
Network Control
SJ100DN Inverter
Low byte
LSB
Hex
0 0 0 0
0060h
FW Run
Low byte
LSB
Hex
0 0 1 0
0062h
RV Run
FW Run
Low byte
LSB
Hex
0 0 0 0
0060h
RV Run
FW Run
Low byte
LSB
Hex
0 0 0 0
0000h
RV Run
FW Run
59
Decimal
96
Decimal
98
Decimal
96
Decimal
00