Program Mode
Primary Central Station Number Communication Format (20)
One location is needed to select the Communication Format to the primary phone number. Address 20 is used for
this purpose. The factory default setting for this address is 'E', which is Contact ID Format. You may enter '0'
through 'D' in place of the default, then press [ENTER/STORE]. Choose from the list of formats below:
0: 4+1 Ademco Express Standard, DTMF, 1400/2300 ACK
1: 4+2 Ademco Express Standard, DTMF, 1400/2300 ACK
2: 3+1 Standard 1800 Hz Carrier, 2300 Hz ACK
3: 3+1 Expanded 1800 Hz Carrier, 2300 Hz ACK
4: 3+1 Standard 1900 Hz Carrier, 1400 Hz ACK
5: 3+1 Expanded 1900 Hz Carrier, 1400 Hz ACK
6: 4+1 Standard 1800 Hz Carrier, 2300 Hz ACK
7: 4+1 Expanded 1800 Hz Carrier, 2300 Hz ACK
8: 4+1 Standard 1900 Hz Carrier, 1400 Hz ACK
9: 4+1 Expanded 1900 Hz Carrier, 1400 Hz ACK
A: 4+2 Standard 1800 Hz Carrier, 2300 Hz ACK
B: 4+2 Expanded 1800 Hz Carrier, 2300 Hz ACK
C: 4+2 Standard 1900 Hz Carrier, 1400 Hz ACK
D: 4+2 Expanded 1900 Hz Carrier, 1400 Hz ACK
E: Contact ID, DTMF, 1400/2300 ACK
F: Future use
Consult the Central Station for proper Format selection. For any Format chosen, all event codes are automati-
cally programmed by the 411UD. Refer to Table 3-2, "4+2 Standard and 4+2 Express Formats - Primary," on
page 28, Table 3-3, "All 3+1, 4+1 and 4+2 Expanded Formats - Primary," on page 29 and Table 3-1, "Ademco
Contact ID Format - Primary," on page 28.
Event Codes - Setting Entries
The Format selected in address 20 will cause the digital communicator to automatically program addresses 138 - 201
with the factory default settings. Any of the Event Code settings may be altered. Consult your Central Station prior
to altering the event code settings. An entry of all zeros for any event code will cause the communicator to NOT
transmit the report. Transmission of reports to either or both Central Station phone numbers may be disabled.
Upon accessing the first address (address 138) shown in Table 3-2 , the following may be displayed on the Program-
mer 7-Segment Display, if the corresponding Format was selected in address 20.
The first three locations on the left of the Programmer display represent the memory address 138 of the Format previ-
ously selected in address 20. The last location 1 (farthest right) represents the contents of memory address 138
(which is the first digit of the event code).
The following Tables list the data which is automatically programmed for each Format that can be selected in address
20. The addresses shown in each Table contain the Setting data which is automatically programmed by the 411UD.
To change the value, key in the new digit and then press the [ENTER/STORE] key to save the new value. Use the
Up and Down Arrow keys to increment to the next address or decrement to the previous address.
1381
(address)(data)
411UD
Document #50759 Rev. E 12/09/2008 P/N 50759:E