Telephone Circuits; Wiring Phone Jacks - Fire-Lite 411UD Manual

Digital alarm communicator/transmitter
Hide thumbs Also See for FIRE-LITE 411UD:
Table of Contents

Advertisement

Telephone Circuits

2.5
Telephone Circuits
Provision to connect two independent telephone lines is available via two telephone jacks labeled PH1 (Primary)
and PH2 (Secondary). Telephone line control/command is possible via double line seizure as well as usage of an
RJ31X style interconnection. (RJ31X jacks must be ordered separately).
CAUTION: It is critical that the 411UD be located as the first device on the incoming telephone circuit to
properly function.

Wiring Phone Jacks

FIGURE 2-5:
411UD
J2
18
(Primary Lines)
Incoming Telco
Phone Lines
Green Wire
Tip
Red Wire
Ring
1 2 3 4 5 6 7 8
RJ31X
JACK
Modular
Female
Connector
PH1
PH2
411UD
Ring
To Premises Phone
Tip
Note: Shorting bars
inside RJ31X Jack
removed during
male plug insertion
7 foot Cable (MCBL-7)
Not supplied - Order
Separately
Primary Phone Line
PH1
Secondary Phone Line
PH2
Male Plug Connectors
Document #50759 Rev. E 12/09/2008 P/N 50759:E
(Secondary Lines)
Incoming Telco
Phone Lines
Green Wire
Tip
Red Wire
Ring
Ring
To Premises
Phone
1 2 3 4 5 6 7 8
RJ31X
JACK
Tip