Hitachi L100 Series Instruction Manual page 91

Hide thumbs Also See for L100 Series:
Table of Contents

Advertisement

3–20
"A" Group: Standard Functions
Second Acceleration and Deceleration Functions
The L100 inverter features two-stage acceleration and deceleration ramps. This gives
flexibility in the profile shape. You can specify the frequency transition point, the point
at which the standard acceleration (F_02) or deceleration (F_03) changes to the second
acceleration (A_92) or deceleration (A_93). Select a transition frequency method via
A_94 as depicted below.
A_94 = 00
Output
frequency
2CH
input
Func.
Name /
Code
SRW Display
A_92 Acceleration (2) time
setting
ACC 2
A_93 Deceleration (2) time
setting
DEC 2
A_94 Select method to switch
to Acc2/Dec2 profile
ACC CHG
A_95 Acc1 to Acc2 frequency
transition point
ACC CHFr 000.0Hz
A_96 Dec1 to Dec2 frequency
transition point
DEC CHFr 000.0Hz
NOTE: For A_95 and A_96, if you set a very rapid Acc1 or Dec1 time (less than 1.0
second), the inverter may not be able to change rates to Acc2 or Dec2 before reaching
the target frequency. In that case, the inverter decreases the rate of Acc1 or Dec1 in order
to achieve the second ramp to the target frequency.
Transition via 2CH input
Accel 2
Accel 1
0
1
0
"A" Function
Description
Duration of 2nd segment of
acceleration, range is:
0.1 to 3000 sec.
0015.0s
Duration of 2nd segment of
deceleration, range is:
0.1 to 3000 sec.
0015.0s
Two options for switching
from 1st to 2nd accel/decel:
00 ...2CH input from terminal
TM
01 ...transition frequency
Output frequency at which
Accel1 switches to Accel2,
range is 0.0 to 360.0 Hz
Output frequency at which
Decel1 switches to Decel2,
range is 0.0 to 360.0 Hz
A_94 = 01
Transition via freq. level
Output
frequency
Accel 2
A 95
Accel 1
0
t
t
Run
Mode
–FE
Edit
(CE)
15.0
15.0
00
0.0
0.0
Frequency
transition point
t
Defaults
–FU
–FR
Units
(UL)
(Jpn)
15.0
15.0
sec.
15.0
15.0
sec.
00
00
0.0
0.0
Hz
0.0
0.0
Hz