Automatic Voltage Regulation (AVR) Function
The automatic voltage regulation (AVR) feature keeps the inverter output waveform at a
relatively constant amplitude during power input fluctuations. This can be useful if the
installation is subject to input voltage fluctuations. However, the inverter cannot boost its
motor output to a voltage higher than the power input voltage. If you enable this feature,
be sure to select the proper voltage class setting for your motor.
"A" Function
Func.
Name /
Code
SRW Display
A_81 AVR function select
AVR MODE
A_82 AVR voltage select
AVR AC
Description
Automatic (output) voltage
regulation, selects from three
DOFF
type of AVR functions, three
option codes:
00 ...AVR enabled
01 ...AVR disabled
02 ...AVR enabled except
during deceleration
200V class inverter settings:
.......200/220/230/240
230V
400V class inverter settings:
.......380/400/415/440/460
L100 Inverter
Defaults
Run
Mode
–FE
–FU
–FR
Edit
(CE)
(UL)
(Jpn)
02
00
230/
230/
200/
400
460
3–19
Units
02
V
400