Reset Inverter

The [RS] terminal causes the inverter to
execute the reset operation. If the inverter is
in Trip Mode, the reset cancels the Trip state.
When the signal [RS] is turned ON and OFF,
the inverter executes the reset operation. The
minimum pulse width for [RS] must be 12 ms
or greater. The alarm output will be cleared
within 30 ms after the onset of the Reset command.
WARNING: After the Reset command is given and the alarm reset occurs, the motor
will restart suddenly if the Run command is already active. Be sure to set the alarm reset
after verifying that the Run command is OFF to prevent injury to personnel.
Option
Terminal
Code
Symbol
18
RS
Reset Inverter
C_01, C_02, C_03, C_04,
Valid for inputs:
C_05
(none)
Required settings:
Notes:
When the control terminal [RS] input is already ON
at powerup for more than 4 seconds, the remote
operator display is "R-ERROR COMM<2>" (the
display of the digital operator [OPE-J] is – – –.
However, the inverter has no error. To clear the
digital operator error, turn OFF the terminal [RS]
input and press one of the operator keys.
Pressing the Stop/Reset key of the digital operator can generate a reset operation only when an alarm
occurs.
A terminal configured with the [RS] function can only be configured for normally open operation. The
terminal cannot be used in the normally closed contact state.
When input power is turned ON, the inverter performs the same reset operation as it does when a pulse
on the [RS] terminal occurs.
The Stop/Reset key on the inverter is only operational for a few seconds after inverter powerup when a
hand-held remote operator is connected to the inverter.
If the [RS] terminal is turned ON while the motor is running, the motor will be free running (coasting).
Input
Function Name
State
ON
OFF
L100 Inverter
1
[RS]
0
Alarm
1
signal
0
Description
The motor output is turned OFF, the Trip Mode
is cleared (if it exists), and powerup reset is
applied
Normal power-ON operation
Example (default input configuration
shown—see page 3–32):
RS
L
5
4
See I/O specs on page 4–6.
4–19
12 ms
minimum
approx. 30 ms
t
3
2
1
P24