Hitachi L100 Series Instruction Manual page 30

Hide thumbs Also See for L100 Series:
Table of Contents

Advertisement

Signal Ratings
Detailed ratings are in
Signal / Contact
Built-in power for inputs
Discrete logic inputs
Discrete logic outputs
PWM (analog/digital) output
Analog input, current
Analog input, voltage
+10V analog reference
Alarm relay contacts
"Specifications of Control and Logic Connections" on page
24VDC, 30 mA maximum
27VDC maximum
50mA maximum ON state current, 27 VDC maximum OFF state voltage
0 to 10VDC, 1 mA, PWM and 50% duty digital
4 to 19.6 mA range, 20 mA nominal
0 to 9.6 VDC range, 10VDC nominal, input impedance 10 kΩ
10VDC nominal, 10 mA maximum
250 VAC, 2.5A (R load) max., 0.2A (I load, P.F.=0.4) max.
100 VAC, 10mA min.
30 VDC, 3.0A (R load) max., 0.7A (I load, P.F.=0.4) max.
5 VDC, 100mA min.
L100 Inverter
Ratings
1–11