Fire-Lite MS-9600 Supplement page 3

Smoke detector capacity detector sensitivity & synchronized strobes positive alarm sequence & printer supervision
Hide thumbs Also See for MS-9600:

Advertisement

II. Addressable Smoke Detector Sensitivity
Software Enhancement
The FACP software has been enhanced to include a feature which allows the control panel to monitor the sensitivity of each
addressable smoke detector in the system. This eliminates the need for a service person to physically connect a sensitivity test
meter to each device in the field.
Detector Data
An addressable smoke detector's ability to detect smoke can change over time as a result of component deterioration due to
environmental contaminants and dirt. Each addressable smoke detector's data (sensitivity) can be printed by entering Read Status
mode.
1. Pressing the Enter or Mode key on the control panel keypad will display the following LCD screen:
2. Press 1 to display the following:
3. Press down arrow key four times to display the following:
4. Press 3 to display the following:
5. Press 3 to print the detector sensitivity data for all addressable smoke detectors installed on the system.
Refer to the sample printout on the following page for information on interpreting the data.
Note: If a printer is not available, it is possible to use the HyperTerminal feature found in the Windows
folder which is resident on most personal computers. Any settings which are configured in this feature must reflect the printer
settings detailed in the FACP manual. Refer to the Windows
1=READ@STATUS
2=PROGRAMMING
@@@@READ@STATUS
1=SYSTEM@POINT
2=ZONES
3=POWER
@@@@READ@STATUS
1=FUTURE@USE
2=PRINTER/PC
3=PRINT
@@@@@@@PRINT
1=HISTORY
2=WALKTEST@LOG
3=DETECTOR@DATA
©
manual for information on the HyperTerminal feature.