Smoke detector capacity detector sensitivity & synchronized strobes positive alarm sequence & printer supervision
Hide thumbs Also See for MS-9600:

Advertisement

5. Press 1 to display the following:
@@@@SYSTEM@SETUP
1=TROUBLE@REM@@OFF
2=BANNER
3=TIME-DATE
6. Press down arrow key once to display the following:
@@@@SYSTEM@SETUP
1=TIMERS
2=NAC
3=RELAYS
7. Press 2 to display the following:
@@@@NACS
1=NAC@1
2=NAC@2
8. Press 1 to program NAC 1 or press 2 to program NAC
2. The following will be displayed (the # symbol will
be replaced by 1 or 2):
@@@@NAC@#
1=ENABLED@@@YES
2=TYPE
3=SILENCEABLE
9. Press 2 to display the following:
@@@@@@@NAC@TYPE
1=BELL
2=HORN
3=STROBE
10. Press down arrow key once to display the following:
@@@@@@@NAC@TYPE
1=SYNCED@STROBE
2=AUDIBLE
3=SIREN@CIRCUIT
Page 2 of 5
11. Press 1 to program the NAC as a synchronized strobe circuit.
The display will return to the following:
@@@@NAC@#
1=ENABLED@@@YES
2=TYPE
3=SILENCEABLE
12. Press the down arrow key three time to display the following:
@@@@@NAC@#
1=SYNC@TYPE
13. Press 1 to display the following:
@@@@@NAC@SYNC@TYPE
1=SYSTEM@SENSOR
2=WHEELOCK
3=GENTEX
14. Select the type of synchronized circuit according to the
manufacturer's devices installed on the NAC by pressing the
corresponding number key. Continue with the programming
of the second NAC if desired.
When all programming is completed, repeatedly press the
ESC (Escape) key to store the program information and exit
Programming mode.
Doc. # 51583 Rev. B 05/07/01 ECN 01-131