Test Time Interval; Account Code - Fire-Lite DACT-UD Manual

Digital alarm communicator/transmitter
Table of Contents

Advertisement

Programming for DACT-UD
CENTRAL STATION
1=TEST TIME INT

2=ACCOUNT CODE

3=24HR TST TIME
Primary/Secondary Screen #1
24

Test Time Interval

Pressing 1 while viewing Primary/Secondary Screen #1 will cause the following
screens to be displayed:
TEST TIME INTERVAL
1=24 HOURS
2=12 HOURS
3=8 HOURS
Test Time Interval Screen #1
TEST TIME INTERVAL
1=6 HOURS
Test Time Interval Screen #2
The test report sent to the Central Station phone number may be sent once every 6,
8, 12 or 24 hours. Select the desired Test Time Interval by pressing the
corresponding digit in the screens shown above.
Account Code
Pressing 2 while viewing Primary/Secondary Screen #1 will cause the following
screen to be displayed:
ACCOUNT CODE
4 CHAR RANGE 0-F
Account Codes Screen
The Account Code, which is assigned by a Central Station, depends on the
communication format being used. The Account Code screen will have a flashing
cursor in the lower left corner. Enter the supplied account code using 0 - 9 and A- F
keys.
Note: If the Account Code being entered is a three digit number, enter the three
digits first and then add a 0 (zero) as the fourth digit.
Programming the MS-9600 Fire Alarm Control Panel
DACT-UD PN 51899:B1 1/25/05