Bryant 312A Installation, Start-Up, Operating And Service And Maintenance Instructions page 29

2-stage deluxe induced-combustion 4-way multipoise furnace installation, start--up, operating and service and maintenance instructions series 120/c
Table of Contents

Advertisement

The Chimney Adapter Kit is a listed alternative venting system
for these furnaces. See the kit instructions for complete details.
Canada (and U.S.A.)- -This furnace is permitted to be vented into
a clay tile- -lined masonry chimney that is exposed to the outdoors
below the roof line, provided:
1. Vent connector is Type- -B double- -wall, and
2. This furnace is common vented with at least 1 draft
hoodequipped appliance, and
3. The combined appliance input rating is less than the
maximum capacity given in Table 8, and
4. The input rating of each space heating appliance is greater
than the minimum input rating given in Table 9 for the
local 99% Winter Design Temperature. Chimneys having
internal areas greater than 38 square inches require furnace
input ratings greater than the input ratings of these
furnaces. See footnote at bottom of Table 9, and
5. The authority having jurisdiction approves.
If all of these conditions cannot be met, an alternative venting
design shall be used, such as the listed chimney adapter kit with a
furnace listed for use with the kit, a listed chimney- -lining system,
or a Type- -B common vent.
Inspections before the sale and at the time of installation will
determine the acceptability of the chimney or the need for repair
and/or (re)lining. Refer to Fig. 35 to perform a chimney
inspection. If the inspection of a previously used tile- -lined
chimney:
a. Shows signs of vent gas condensation, the chimney
should be relined in accordance with local codes and the
authority having jurisdiction. The chimney should be
relined with a listed metal liner, Type- -B vent, or a listed
chimney adapter kit shall be used to reduce condensation.
If a condensate drain is required by local code, refer to
the NFGC, Section 10.9 for additional information on
condensate drains.
b. Indicates the chimney exceeds the maximum permissible
size in the tables, the chimney should be rebuilt or relined
to conform to the requirements of the equipment being
installed and the authority having jurisdiction.
A chimney without a clay tile liner, which is otherwise in good
condition, shall be rebuilt to conform to ANSI/NFPA 211 or be
lined with a UL listed (ULC listed in Canada) metal liner or UL
listed Type- -B vent. Relining with a listed metal liner or Type- -B
vent is considered to be a vent- -in- -a- -chase.
If a metal liner or Type- -B vent is used to line a chimney, no other
appliance shall be vented into the annular space between the
chimney and the metal liner.
Exterior Masonry Chimney FAN + NAT
Installations with Type- -B Double- -Wall Vent
Connectors ENFPA & AGA
Table 8 – Combined Appliance Maximum Input Rating in
Thousands of BTUH per Hour
INTERNAL AREA OF CHIMNEY
VENT HEIGHT
(FT)
12
6
74
8
80
10
84
15
NR
20
NR
30
NR
(SQ. IN.)
19
28
38
119
178
257
130
193
279
138
207
299
152
233
334
NR
250
368
NR
NR
404
Table 9 – Minimum Allowable Input Rating of Space- -Heat-
ing Appliance in Thousands of BTUH per Hour
INTERNAL AREA OF CHIMNEY
VENT HEIGHT
(FT)
12
Local 99% Winter Design
Temperature: 17 to 26_F
6
0
8
52
10
NR
15
NR
20
NR
30
NR
Local 99% Winter Design
Temperature: 5 to 16_F*
6
NR
8
NR
10
NR
15
NR
20
NR
30
NR
Local 99% Winter Design
Temperature: ---10 to 4_F*
6
NR
8
NR
10
NR
15
NR
20
NR
30
NR
Local 99% Winter Design
Temperature: ---11_F or lower
Not recommended for any vent configuration.
*The 99% Winter Design Dry ---Bulb (db) temperatures are found in the
1993 ASHRAE Fundamentals Handbook, Chapter 24, Table 1 (United
States) and 2 (Canada), or use the 99.6% heating db temperatures found
in the 1997 or 2001 ASHRAE Fundamentals Handbook, Climatic Design
Information chapter, Table 1A (United States) and 2A (Canada).
APPLIANCE APPLICATION REQUIREMENTS
Appliance operation has a significant impact on the performance
of the venting system. If the appliances are sized, installed,
adjusted, and operated properly, the venting system and/or the
appliances should not suffer from condensation and corrosion.
The venting system and all appliances shall be installed in
accordance with applicable listings, standards, and codes.
The furnace should be sized to provide 100% of the design
heating load requirement plus any margin that occurs because of
furnace model size capacity increments. Heating load estimates
can be made using approved methods available from Air
Conditioning Contractors of America (Manual J); American
Society of Heating, Refrigerating, and Air- -Conditioning
Engineers; or other approved engineering methods. Excessive
over- -sizing of the furnace could cause the furnace and/or vent to
fail prematurely. When a metal vent or metal liner is used, the
vent must be in good condition and be installed in accordance
with the vent manufacturer's instructions.
To prevent condensation in the furnace and vent system, the
following precautions must be observed:
1. The return- -air temperature must be at least 60_F db except
for brief periods of time during warm- -up from setback at
no lower than 55_F (13_C) db or during initial start- -up
from a standby condition.
2. Adjust the gas input rate per the installation instructions.
Low gas input rate causes low vent gas temperatures,
29
(SQ. IN.)
19
28
38
55
99
141
74
111
154
90
125
169
NR
167
212
NR
212
258
NR
NR
362
78
121
166
94
135
182
111
149
198
NR
193
247
NR
NR
293
NR
NR
377
NR
145
196
NR
159
213
NR
175
231
NR
NR
283
NR
NR
333
NR
NR
NR

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents