Physical Data; Vapor Line Sizing And Cooling Capacity Loss; Long Line Application - Bryant LEGACY 124A Product Data

Legacy line 14 air conditioner with puron refrigerant 1-1/2 to 5 tons (sizes 018 to 060)
Table of Contents

Advertisement

UNIT SIZE --- SERIES
Operating Weight lb (kg)
Shipping Weight lb (kg)
Compressor Type
REFRIGERANT
Control
Charge lb (kg)
COND FAN
Air Discharge
Air Qty (CFM)
Motor HP
Motor RPM
COND COIL
Face Area (Sq ft.)
Fins per In.
Rows
Circuits
VALVE CONNECT. (In. ID)
Vapor
Liquid
REFRIGERANT TUBES (In. OD)
Rated Vapor*
Liquid
*Units are rated with 25 ft (7.6 m) of lineset length. See Vapor Line Sizing and Cooling Capacity Loss table when using other sizes and lengths of lineset.

VAPOR LINE SIZING AND COOLING CAPACITY LOSS

LONG LINE APPLICATION: An application is considered
"Long line" when the total equivalent tubing length exceeds 80
ft. (24.38 m) or when there is more than 20 ft. (6.09 m) vertical
separation between indoor and outdoor units. These applications
require additional accessories and system modifications for
reliable system operation. The maximum allowable total
equivalent length is up to 250 ft. (76.2 m). The maximum
Unit
Maximum
Vapor Line
Nominal
Liquid Line
Diameters
Size
Diameters
(In. OD)
(Btuh)
(In. OD)
18000
1/2
1 Stage
3/8
5/8
Puron AC
5/8
24000
1 Stage
3/4
3/8
Puron AC
7/8
5/8
30000
1 Stage
3/8
3/4
Puron AC
7/8
5/8
36000
1 Stage
3/4
3/8
Puron AC
7/8
3/4
42000
1 Stage
3/8
7/8
Puron AC
1 1/8
3/4
48000
1 Stage
3/8
7/8
Puron AC
1 1/8
3/4
60000
1 Stage
7/8
3/8
Puron AC
1 1/8
Applications in this area are long line. Accessories are required as shown recommended on Long Line Application Guidelines
Applications in this area may have height restrictions that limit allowable total equivalent length, when outdoor unit is below indoor unit See Long Line Applica-
tion Guidelines

PHYSICAL DATA

018---C
024---D
195 (88.4)
184 (83.5)
223 (101.2)
223 (101.2)
5.4 (2.45)
5.48 (2.49)
2235
3223
1/12
1/12
800
800
19.40
17.60
25
25
1
1
3
4
5/8
5/8
5/8
Standard
Application
26--- 50
51--- 80
81--- 100
(7.9--- 15.2)
(15.5--- 24.4)
(24.7--- 30.5)
1
2
3
0
0
1
0
1
1
0
0
0
0
0
0
1
2
3
0
0
1
0
0
0
1
2
4
0
0
1
0
0
0
0
1
2
0
0
1
0
0
0
0
1
2
0
0
1
0
0
0
1
2
4
0
1
2
0
0
0
030---D
036---C
042---D
177 (80.3)
225 (102.1)
228 (103.4)
218 (98.9)
259 (117.5)
267 (121.1)
Scroll
Puron® (R--- 410A)
TXV (Puron® Hard Shutoff)
5.8 (2.63)
6.97 (3.16)
9.5 (4.31)
Propeller Type, Direct Drive
Vertical
3223
3810
3810
1/12
1/5
800
800
17.60
22.63
17.60
25
25
1
1
4
5
3/4
3/4
3/8
3/4
3/8
vertical separation is 200 ft. (60.96 m) when outdoor unit is
above indoor unit, and up to 80 ft. (24.38 m) when the outdoor
unit is below the indoor unit. Refer to Accessory Usage Guideline
below for required accessories. See Longline Application
Guideline for required piping and system modifications. Also,
refer to the table below for the vapor tube diameters based on the
total length to minimize the cooling capacity loss.
Cooling Capacity Loss (%)
Total Equivalent Line Length ft. (m)
Long Line Application Requires Accessories
101--- 125
126--- 150
151--- 175
(30.8--- 38.1)
(38.4--- 45.7)
(46.0--- 53.3)
4
6
7
1
1
2
2
3
3
0
1
1
0
0
0
3
4
5
1
1
2
0
1
1
5
6
7
1
2
2
0
1
1
2
3
4
1
1
2
0
0
0
3
4
5
1
2
2
0
0
0
5
6
7
2
3
4
1
1
1
3
048---C
060---C
270 (122.5)
337 (152.9)
303 (137.4)
372 (168.7)
11 (4.99)
13.3 (6.03)
3810
4050
1/5
1/5
1/4
800
800
800
20.12
30.18
20
20
20
2
2
2
7
7
7
7/8
7/8
7/8
7/8
1--- 1/8
176--- 200
201--- 225
226--- 250
(53.6--- 61.0)
(61.3--- 68.6)
(68.9--- 76.2)
8
9
10
2
3
3
4
4
5
1
1
1
0
0
0
6
7
8
2
2
3
1
1
1
9
10
11
3
3
4
1
1
2
4
5
6
2
2
3
0
0
0
5
6
7
2
3
3
0
1
1
9
10
11
4
5
5
1
1
1

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents