Electrical Data; A- -Weighted Sound Power; Charging Subcooling - Bryant LEGACY 124A Product Data

Legacy line 14 air conditioner with puron refrigerant 1-1/2 to 5 tons (sizes 018 to 060)
Table of Contents

Advertisement

ELECTRICAL DATA

OPER
UNIT
VOLTS*
SIZE ---
V/PH
SERIES
MAX
018---C
024---D
030---D
036---C
208/230/1
253
042---D
048---C
060---C
* Permissible limits of the voltage range at which the unit will operate satisfactorily
{ If wire is applied at ambient greater than 30° C, consult table 310 ---16 of the NEC (ANSI/NFPA 70). The ampacity of non ---metallic---sheathed cable (NM),
trade name ROMEX, shall be that of 60° C conditions, per the NEC (ANSI/NFPA 70) Article 336 ---26. If other than uncoated (no ---plated), 60 or 75° C
insulation, copper wire (solid wire for 10 AWG or smaller, stranded wire for larger than 10 AWG) is used, consult applicable tables of the NEC (ANSI/NFPA
70).
Length shown is as measured 1 way along wire path between unit and service panel for voltage drop not to exceed 2%.
}
** Time ---Delay fuse.
FLA --- Full Load Amps
LRA --- Locked Rotor Amps
MCA --- Minimum Circuit Amps
RLA --- Rated Load Amps
NOTE: Control circuit is 24 ---V on all units and requires external power source. Copper wire must be used from service disconnect to unit.
All motors/compressors contain internal overload protection.
Complies with 2001 requirements of ASHRAE Standards 90.1

A- -WEIGHTED SOUND POWER

UNIT SIZE ---
STANDARD
VOLTAGE,
RATING
SERIES
(dBA)
018--- C
73
024--- D
74
030--- D
74
036--- C
72
042--- D
74
048--- C
73
060--- C
74
NOTE: Tested in accordance with ARI Standard 270 ---95. (Not listed with ARI).
CHARGING SUBCOOLING (TXV- -TYPE EXPANSION DEVICE)
UNIT SIZE ---VOLTAGE, SERIES
018---C
024---D
030---D
036---C
042---D
048---C
060---C
COMPR
MIN
LRA
RLA
48.0
9.0
58.3
13.5
73.0
14.1
197
79.0
16.7
112.0
17.9
117.0
21.8
134.0
26.4
TYPICAL OCTAVE BAND SPECTRUM (dBA, without tone adjustment)'
125
250
56.0
60.0
51.0
60.0
53.0
62.0
52.0
62.0
60.0
65.5
59.5
63.5
55.5
64.0
MIN
MIN WIRE
FAN
WIRE
MCA
SIZE{
FLA
60° C
0.5
11.7
14
0.5
17.3
14
0.5
18.1
14
1.2
22.0
12
1.2
23.6
12
1.2
28.4
10
1.2
34.2
8
500
1000
65.0
69.0
66.5
66.5
68.5
69.0
65.5
67.5
68.5
68.5
66.5
67.5
67.0
69.0
REQUIRED SUBCOOLING _F (_C)
7
MAX
MAX
LENGTH
LENGTH
SIZE{
ft. (m)}
ft. (m)}
75° C
60° C
75° C
14
67 (20.4)
64 (19.5)
14
46 (14.0)
43 (13.1)
14
44 (13.4)
41 (12.5)
12
57 (17.4)
54 (16.5)
10
53 (16.2)
50 (15.2)
10
70 (21.3)
67 (20.4)
8
91 (27.7)
86 (26.2)
2000
4000
63.0
60.0
64.0
60.0
65.5
61.0
63.0
61.0
65.0
60.0
64.0
62.0
65.0
60.0
10 (5.6)
10 (5.6)
11 (6.1)
10 (5.6)
12 (6.7)
9 (5.0)
9 (5.0)
MAX
FUSE**
or CKT
BRK
AMPS
15
30
30
35
40
40
50
8000
52.5
52.5
54.0
53.5
52.5
55.5
54.5