Setting a Thermostat Jumper for
Setting a Thermostat Jumper for
Dehumidification Operation
Dehumidification Operation
To control a MISC outputs dehumidification, install the Humidity
Module and place the Humidity Jumper on HUM (see page 9.2).
Then place the MISC1, MISC2, or MISC3 jumper on the terminal
labeled DEHUM (see diagram below). This will supply 24VAC to the
selected MISC terminal based on the programming in the following
pages. Only one of the three outputs (MISC1, MISC2, or MISC3) is
required to have a jumper. For more information regarding the MISC1,
MISC2, and MISC3 outputs, please see section 17.
In the diagram below, the MISC2 jumper has
10
been set for DEHUM (dehumidification) operation.
ELEC
GAS
W3
HP
HUM
GAS
DEHUM
Y2
B
(MISC1
MISC3
MISC2
MISC1
O
ONLY)
W1
Y1
G
MISC2
R
INSTALL HUMIDITY
MODULE WITH SENSING
ELEMENT OUTWARD
C
MISC3
MISC3
OK
W3
HUM
W2
DEHUM
MISC1
RS2
MISC3
RS+5
MISC3
MISC2
RSGND
IMPORTANT CAUTION
NEVER PUT MORE THAN ONE JUMPER
ON THE SAME MISC JUMPER BLOCK!
THIS MAY DAMAGE THE THERMOSTAT.
Page 10.2
Carrier
Y2
(MISC1
MISC1
ONLY)