Closed System/Thermal Expansion - A.O. Smith Water Heater User Manual

A.o. smith water heater user manual
Table of Contents

Advertisement

HOTWA_--T_
OUTLET
IN A CLOSED SYSTEM
USE A
_..THERMAL
EXPANSION
TANK
COLD WATER SUPPLY TO FIXTURES
PRESSURE
REDUCING
VALVE
H BYPASS
D WATER
INLET
COLD WATER INLET VALVE
(SHUT-OFF
VALVE)
TEMPERATURE
AND PRESSURE
(T&P)
RELIEF VALVE (OPTIONAL
TOP T&P
RELIEF VALVE NOT SHOWN)
i,---- DISCHARGE
PIPE
(DO NOT CAP OR PLUG)
MASSACHUSETTS:
INSTALL
DRAIN LINE
I A VACUUM
RELIEF IN COLD
3/4" ID
I WATER LINE PER SECTION
.
_
MINIMUM
119MGL
142.
1" MINIMUM--_
,.,_-J_
_/
METAL
I
+It] _Jl.rF
/_'- _6"
MAXIMUM
DRAIN PAN-_'
"
_
AIR GAP
DRAIN_
v_-'-
FIGURE 13.
Please note the following:
The system should be installed only with piping that is
suitable for potable (drinkable) water such as copper,
CPVC, or polybutylene. This water heater must not be
installed using iron piping or PVC water piping.
Use only pumps, valves, or fittings that are compatible
with potable water.
It is recommend that only full flow ball or gate valves
are used in water piping installations. The use of valves
that may cause excessive restriction to water flow is not
recommended.
Use only 95/5 tin-antimony or other equivalent solder.
Any lead based solder must not be used.
Piping that has been treated with chromates, boiler seal,
or other chemicals must not be used.
Chemicals that may contaminate the potable water
supply must not be added to the piping system.
Closed
System/Thermal
Expansion
Prope_y Damage Hazard
• All water heaters eventual!y !eak
• Do notinstallwithoutadequate
drainage,
UNTEMPERED
HOT WATER
TO FIXTURES
COLD
WATER
INLET
HOT
OUTLET
TEMPERING
VALVE//_
(SET TO 120°F)
II
FOLLOW
THE TEMPERING
VALVE
MANUFACTURER'S
INSTRUCTIONS
FIGURE 14.
Periodic discharge of the temperature and pressure relief valve
may be due to thermal expansion in a closed water supply
system. The water utility supply meter may contain a check valve,
backflow preventer or water pressure reducing valve. This wilt
create a closed water system. During the heating cycle of the
water heater, the water expands causing pressure inside the
water heater to increase. This may cause the temperature
and
pressure relief valve to discharge small quantities of hot water. To
prevent this, it is recommended
that a diaphragm-type
expansion
tank (suitable for potable water) be installed on the cold water
supply line. The expansion tank must have a minimum capacity of
1.5 U.S. gallons for every 50 gallons of stored water. Contact the
local water supplier or plumbing inspector for information on other
methods to control this situation.
16

Advertisement

Table of Contents
loading

Table of Contents