LP Gas Only
Explosion
Hazard
Have a qualified person make sure L.P. gas pressure
does not exceed 13" water column.
Examples of a qualified person include: licensed
plumbers, authorized gas company personnel, and
authorized service personnel.
Failure to do so can result in death, explosion, or fire.
Liquefied petroleum gas is over 50% heavier than air
and in the occurrence of a leak in the system, the gas
will settle at floor level. Basements, crawl spaces, closets
and areas below ground level will serve as pockets for
the accumulation of gas. Before lighting an L.R gas water
heater, smell all around the appliance at floor level. If you
smell gas, follow the instructions as given in the warning
on the front page.
When your L.P. tank runs out of fuel, turn off the gas at
all gas appliances including pilot lights. After the tank is
refilled, all appliances must be re-lit according to their
manufacturer's
instructions.
Table
1
Natural
Gas Pipe Capacity
Table (Cu. Ft./Hr.)
Capacity of gas pipe of different diameters and lengths in cu. ft. per hr. with pressure drop of 0.3 in. and specific gravity
of 0.60 (natural gas).
Nominal Iron Pipe
Length of Pipe, Feet
Size, in.
10
20
30
40
50
60
70
80
90
100
125
150
175
200
112
132
92
73
63
56
50
46
43
40
38
34
3!
28
26
3/4
278
190
152
130
115
105
96
90
84
79
72
64
59
55
1
520
350
285
245
215
195
180
170
160
150
130
120
110
100
1-1/4
1050
730
590
500
440
400
370
350
320
305
275
250
225
210
1-1/2
1600
1100
890
760
670
610
560
530
490
460
410
380
350
320
After the length of pipe has been determined, select the pipe size which will provide the minimum cubic feet per hour
required for the gas input rating of the water heater. By formula:
Gas Input of Water Heater (BTU/HR)
Cu. Ft. Per Hr. Required=
Heating Value of Gas (BTU/FT 3)
The gas input of the water heater is marked on the water heater data plate. The heating value of the gas (BTU/FT 3)
may be determined
by consulting
the local natural gas utility.
Table 2
LP Gas Capacity
Table
Maximum capacity of pipe in thousands of BTU per hour of undiluted liquefied petroleum gases (at 11 inches water
column pressure). Based on a pressure drop of 0.5 inch water column.
Nominallron
Pipe
Length ofPipe, Feet
Size, in.
1__0_____Z0_______5_0_
7__
1/2
275
189
152
129
114
103
96
3/4
576
393
315
267
237
217
196
1
1071
732
590
504
448
409
378
1-1_
2205
1496
1212
1039
913
834
771
.__SD____9_0___l__L0_0___.J25_1__15_D_
89
83
78
69
63
185
173
162
146
132
346
322
307
275
252
724
677
630
567
511
Example:
Input BTU requirement
of the water heater 100,000 BTUH.
Total pipe length, 80 feet = 3/4" IPS required.
Additional
tables are available
in the latest edition of the "National
Fuel Gas Code", ANSI Z223.1.