v Follow the suggested actions in the order in which they are listed in the Action column until the problem is
solved.
v See Chapter 4, "Parts listing," on page 41 to determine which components are CRUs and which components
are FRUs.
v If an action step is preceded by "(Trained service technician only)," that step must be performed only by a
trained service technician.
Error Code
Type
0x80010900
Error
0x80010900
Error
0x80010900
Error
108
BladeCenter HS22 Type 7870, 1936, and 1911: Problem Determination and Service Guide
Error Message
Expansion Module 1 (BPE3 12V
Sense) voltage under critical
threshold. with chassis Reading:
X, Threshold: Y
Expansion Module 1 (BPE3
12VSB Sense) voltage over
critical threshold. Reading: X,
Threshold: Y
Expansion Module 1 (BPE3 3.3V
Sense) voltage under critical
threshold. with chassis Reading:
X, Threshold: Y
Action
1. If the under voltage problem is occurring on all
blade servers, look for other events in the log
related to power and resolve those events (see
"Error logs" on page 103).
2. View the event log provided by the advanced
management module for your BladeCenter unit
and resolve any power related errors that might
be displayed.
3. If other modules or blades are logging the same
issue then check the power supply for the
BladeCenter unit.
4. If the error continues, replace the Blade PCI
Express I/O expansion unit. See "Removing an
optional expansion unit" on page 84 and
"Installing an optional expansion unit" on page
85.
1. If the over voltage problem is occurring on all
blade servers, look for other events in the log
related to power and resolve those events.
2. View the event log provided by the advanced
management module for your BladeCenter unit
and resolve any power related errors that might
be displayed.
3. If other modules or blades are logging the same
issue then check the power supply for the
BladeCenter unit.
4. If the error continues, replace the Blade PCI
Express I/O expansion unit. See "Removing an
optional expansion unit" on page 84 and
"Installing an optional expansion unit" on page
85.
1. If the under voltage problem is occurring on all
blade servers, look for other events in the log
related to power and resolve those events.
2. View the event log provided by the advanced
management module for your BladeCenter unit
and resolve any power related errors that might
be displayed.
3. If other modules or blades are logging the same
issue then check the power supply for the
BladeCenter unit.
4. If the error continues, replace the Blade PCI
Express I/O expansion unit. See "Removing an
optional expansion unit" on page 84 and
"Installing an optional expansion unit" on page
85.