CLEARANCES FROM COMBUSTIBLES
It is of outmost importance that the clearances to combustible materials be scrupulously
respected upon installation of the stove you have selected. Refer to the tables below :
Model
Eldorado
Adirondack
Savannah
Celtic
Jurassien
•
Floor to ceiling height must be at least 7' (84") in all cases.
•
The clearance between the flue pipe and a wall are valid only for vertical walls and for
vertical flue pipe.
•
The flue pipe must not go through roof trussing, an attic, a wardrobe, a floor, a
combustible partition, or similar spaces.
•
A flue pipe crossing a combustible wall must have a minimum clearance of 18".
•
To reduce flue pipe clearances from combustible materials, contact your local safety
department.
Single pipe / Double pipe
A
B
15/6
18/18
15/5
12/12
15/6
18/18
15/5
12/12
14/7
8/8
C
D
12/12
21.5/12.5 30.5/30.5
10/8
21.5/11.5 24.5/24.5
12/12
21.5/12.5 30.5/30.5
10/8
21.5/11.5 24.5/24.5
10/6
20.8/13.7 23.5/23.5 22.2/18.2
E
F
24/24
22/20
24/24
22/20
10