CLEARANCES FROM COMBUSTIBLES

It is of outmost importance that the clearances to combustible materials be scrupulously
respected upon installation of the stove you have selected. Refer to the tables below :
Model
AUSTRAL
BALTIC
LEGEND
MYRIAD
Floor to ceiling height must be at least 7' (84") in all cases.
The clearance between the flue pipe and a wall are valid only for vertical walls and for
vertical flue pipe.
The flue pipe must not go through roof trussing, an attic, a wardrobe, a floor, a
combustible partition, or similar spaces.
A flue pipe crossing a combustible wall must have a minimum clearance of 18".
To reduce flue pipe clearances from combustible materials, contact your local safety
department.
NorthlineExpress.com
Single pipe / Double pipe
A
B
7/6
23/24
16/17
6/6
12/12
8.5/8.5
6/6
12/12
8.5/8.5
7/6
23/24
16/17
http://www.northlineexpress.com
C
D
13.7/12.7 34.9/35.9 27.9/28.9
12.7/12.7 23.9/23.9 20.4/20.4
12.7/12.7 23.9/23.9 20.4/20.4
13.7/12.7 34.9/35.9 27.9/28.9
E
F
10