Select A Location - NETGEAR GSM7352SNA - Prosafe 48 Port Gigabit L3 Managed Stackable Switch Installation Manual

Managed stackable layer 3 switches
Table of Contents

Advertisement

Managed Stackable Layer 3 Switches GSM7328S, GSM7352S and GSM7328FS Hardware Instal-

Select a Location

The switch can be mounted in a standard 19-inch (48.26-centimeter) rack, wall-
mounted, or left freestanding (placed on a tabletop).
The site where you install the switch may greatly affect its performance. Before
installing the switch or switches, make sure that the chosen installation location
meets the following site requirements.
Table 3-1. Site Requirements for Switch Location
Requirements
Mounting
Access
Power source
Environment
Temperature
Operating humidity
Ventilation
Cabling
3-4
• Desktop Installations: Provide a flat table or shelf surface.
• Rack-mount Installations: Use a 19-inch (48.3-centimeter) EIA
standard equipment rack that is grounded and physically
secure. You need the rack-mount kit supplied with your switch.
Locate the switch in a position that lets you access the front
panel RJ-45 ports, view the front panel LEDs, and access the
rear-panel power connector.
Provide a power source within 6 feet (1.8 meters) of the
installation location. Power specifications for the switch are
shown in Appendix A, "Technical Specifications". Be sure that
the AC outlet is not controlled by a wall switch, which can
accidentally turn off power to the outlet and the switch.
Install the switch in a site free from strong electromagnetic field
generators (such as motors), vibration, dust, and direct
exposure to sunlight.
The ambient switch operating temperature range is 0º to 55ºC
(32º and 131ºF). Keep the switch away from heat sources such
as direct sunlight, warm air exhausts, hot-air vents, and heaters.
Install the switch in a dry area with a maximum relative humidity
of 90%, noncondensing.
Do not restrict airflow by covering or obstructing air inlets on the
sides of the switch. Keep at least 2 inches (5.08 centimeters)
free on all sides for cooling. Be sure that there is adequate
airflow in the room or wiring closet where you intend to install the
switch.
Route the cable to avoid sources of electrical noise such as
radio transmitters, broadcast amplifiers, power lines, and
fluorescent lighting fixtures.
v1.0, February 2007
Hardware Installation

Advertisement

Table of Contents
loading

Table of Contents