Connecting To Gas Supply - Vanguard VP10TA Owner's Operation And Installation Manual

Infrared vent-free propane/lp gas heater
Table of Contents

Advertisement

INSTALLATION
Continued
CONNECTING TO GAS
SUPPLY
WARNING: This appliance re-
quires a 3/8" NPT (National Pipe
Thread) inlet connection to the
pressure regulator.
WARNING: A qualified service
person must connect heater to gas
supply. Follow all local codes.
CAUTION: Never connect heater
directly to the propane/LP supply.
This heater requires an external
regulator (not supplied). Install the
external regulator between the
heater and propane/LP supply.
The installer must supply an external regu-
lator. The external regulator will reduce
incoming gas pressure. You must reduce
incoming gas pressure to between 11 and 14
inches of water. If you do not reduce incom-
ing gas pressure, heater regulator damage
could occur. Install external regulator with
the vent pointing down as shown in Figure
12. Pointing the vent down protects it from
freezing rain or sleet.
CAUTION: Use only new,
black iron or steel pipe. Inter-
nally-tinned copper tubing may
be used in certain areas. Check
your local codes. Use pipe 3/8"
diameter or greater to allow
proper gas volume to heater. If
pipe is too small, undue loss of
pressure will occur
104083
Installation must include a equipment shutoff
valve, ground joint union, and plugged 1/8"
NPT tap. Locate NPT tap within reach for
test gauge hook up. NPT tap must be up-
stream from heater (see Figure 13). An
appliance main gas valve (equipment shutoff
valve) shall be provided in an accessible
location for turning on or shutting off the
gas to the appliance.
Propane/
LP Supply
Tank
Figure 12 - External Regulator With Vent
Pointing Down
3/8" NPT
Pipe
Nipple
Equipment
Shutoff
Valve *
From External
Regulator
(11" W.C. to
14" W.C.
Pressure)
3" Minimum
Figure 13 - Gas Connection
* A CSA/AGA design-certified equipment shutoff valve with 1/8" NPT tap is an acceptable
alternative to test gauge connection. Purchase the optional CSA/AGA design-certified
equipment shutoff valve from your dealer. See Accessory, page 18.
9
OWNER'S MANUAL
IMPORTANT: Install an equipment shutoff
valve in an accessible location. The equip-
ment shutoff valve is for turning on or
shutting off the gas to the appliance.
Apply pipe joint sealant lightly to male
threads. This will prevent excess sealant
from going into pipe. Excess sealant in pipe
could result in clogged heater valves.
CAUTION: Use pipe joint seal-
ant that is resistant to liquid pe-
troleum (LP) gas.
Install sediment trap in supply line as shown
External
Regulator
in Figure 13. Locate sediment trap where it
is within reach for cleaning. Locate sedi-
ment trap where trapped matter is not likely
to freeze. A sediment trap traps moisture
and contaminants. This keeps them from
Vent
Pointing
going into heater controls. If sediment trap
Down
is not installed or is installed wrong, heater
may not run properly.
IMPORTANT: Hold pressure regulator
with wrench when connecting it to gas pip-
ing and/or fittings.
Pressure
Regulator
Heater
Cabinet
Ground Joint
Union
Tee Joint
Reducer
Bushing to
1/8" NPT
1/8" NPT
Plug Tap
Tee
Joint
Sediment
Pipe
Trap
Nipple
Cap
Test
Gauge
Connection *
Continued